D9112B | Program Entry Guide | 7.0
2
Interior: Interior points are armed only by master arming the area. They are NOT armed when
using perimeter arming commands (COMMAND 2, COMMAND 3, and COMMAND 8). These
points are typically used to monitor interior detection devices such as interior doors, motion
detectors, photoelectric beams, carpet mats, and so on.
Instant Interior Points: Interior points are usually programmed for an instant alarm (see
Response
or exit delay.
Delayed Interior Points: Interior points can be programmed for a delayed
delayed response means that if the point is tripped while the area is armed, it initiates entry delay. It
does not generate an alarm until entry delay expires.
When an interior point is programmed for entry delay, entry delay time is always provided. If the
area is in entry delay when the interior point trips, the panel compares the remaining entry delay
time to the time programmed for the interior point. If the interior point's entry delay time is less
than the remaining time, it shortens the entry delay time.
Delayed points can also initiate an entry tone at the command center (see P## Entry Tone Off).
Note:
In some cases you may need to create an interior point that causes an instant alarm only if entry delay
protection is not tripped first. Use Interior Follower to create this type of protection.
3
Interior Follower: Interior follower points are armed only by master arming the area. They are
NOT armed when using perimeter arming commands (COMMAND 2, COMMAND 3, and
COMMAND 8).
An interior follower point does not create an alarm if it trips while the area is in entry delay. An
interior follower does not change the amount of remaining entry delay time.
In no entry delay is in effect when the interior follower trips, it creates an instant alarm.
You must program a delayed
panel ignores the entry in
Bosch Security Systems | 2/04 | 74-06145-000-D
Point Index
). Points programmed for instant alarms generate alarms immediately, even during entry
Point Response
P## Entry Delay
(4, 5, 6, 7, or 8) for an Interior Follower point. The
for an Interior Follower point.
EN | 70