Powering Up; Programming The Control Panel; Installing The Point Chart Label; Testing The System - Bosch D7212GV3 Operation And Installation Manual

Hide thumbs Also See for D7212GV3:
Table of Contents

Advertisement

.
4.6.5

Powering Up

Reconnect the battery, then plug in the transformer.
The buzzer sounds for two sec when the control panel
is powered up. Leave the reset pin in the locked
position.
Yellow Charging Status LED Remains Lit: If the
yellow charging status LED remains lit after five
minutes of powering up the control panel, either the
battery is deeply discharged, or too many powered
devices were connected to the control panel.
Combined continuous current draw for Terminals 38,
24, and 32, and the accessory connector cannot
exceed 1.4 A. Refer to Section 6.0 Power Outputs on
page 24 for help.
4.7

Programming the Control Panel

If the control panel is not already programmed, review
the D7212GV3 Program Entry Guide
(P/N: F01U170808). Ensure that all accessory
modules for desired features are available for
installation.
Use RPS to load a custom program into the control
panel as needed.
4.8

Installing the Point Chart Label

The point chart label is required for fire
systems with verifications points.
A point chart label is included in the literature pack.
Install the point chart label for fire or combined fire-
and-burglary systems that use verification points.
Use the D7212GV3 Program Record Sheet
(P/N: F01U170810) to gather the necessary
information for completing the point chart. Fill out the
label and install it on the inside of the enclosure door
(refer to Figure 2 on page 14).
Avoid smearing the entries on the chart.
Use the peel-off backing to press the label
in place.
Bosch Security Systems, Inc. | 10/10 | F01U143079-03
D7212GV3 | Operation and Installation Guide | 4.0
4.9

Testing the System

After installing and programming the control panel,
test the system completely. Test the control panel and
all devices for proper operation.
Test after initially programming the control
panel and after subsequent programming
changes.
Refer to Section 4.10 Service Walk Test for complete
Service Walk Test instructions.
Clear after Test: To clear the event memory and
report buffer, momentarily close the reset pin. Events
stored in the control panel's event log are not cleared.
4.10

Service Walk Test

The Service Walk Test differs from the standard Walk
Test. In the standard Walk Test, POPITs whose
switches are set for a point number not programmed
in the control panel do not appear in the test. In the
Service Walk Test, POPITs whose switches are set
for a point number that is not programmed in the
control panel do appear in the test.
The Service Walk Test allows the installer to walk test
all points from a control-panel-wide keypad,
regardless of the point index type.
A Service Walk Test can also be initiated by account-
wide or area-wide keypads but test only those points
that are within the scope of the keypad that initiated
the function. The Service Walk Test does not test
points in armed areas.
Only Walk Test Start and Walk Test End
are reported to the central station.
The D9131A can be configured for local
printing. Refer to the D7212GV3 Program
Entry Guide (P/N: F01U170808).
During a Service Walk Test, the summary
alarm and summary fire remain off, because
there are no Fire or Burg alarm conditions
to summarize. The P# Relay Response
Type feature operates as programmed.
Installation
17

Advertisement

Table of Contents
loading

Table of Contents