P## Bypassable; P## Swinger Bypass; P## Report Bypass At Occurrence - Bosch D9112B Program Entry Manual

Control panel
Table of Contents

Advertisement

D9112B | Program Entry Guide | 7.0

P## Bypassable

Bypass and force arm the point. Points can be bypassed by entering the Bypass a Point function at a command
center, a RAM II command, or a "Bypass a Point" SKED.
To automatically return a bypassed point to the system when disarming, program
you can use Unbypass a Point (Command 00), RAM II UNBYPASS command, or "Unbypass a Point" SKED.
When a controlled point is force armed, it can return to the system when the fault clears if
programmed YES. If it is not returnable, the point stays out of the system until the area is disarmed.
If the panel is reset while a point is bypassed, a
returns to normal.
Default:
No
Selection:
Yes or No
Yes
This point can be bypassed and force armed.
Note:
24-hour points can be bypassable, but the application should be carefully considered.
Report Bypass at Occurrence
When a 24-hour point is bypassed, the report should be sent as it occurs. If the area does not send a
Closing report, a Deferred Bypass report is not sent.
Instead of programming a bypassable 24-hour point, consider a bypassable perimeter point type with a
Point Response
entered, but perimeter points do.
No
This point cannot be bypassed or force armed from the command center or RAM II. However, it
can be force armed by automatic arming at the end of the closing window (see Opening & Closing
Auto Close

P## Swinger Bypass

Automatically bypass a point if it generates four
alarms or four troubles during one clock hour (for
example, between 2:00 and 2:59). If the point has a
partial count (less than four events during an hour),
the count is reset to zero on the hour.
To return a swinger bypass point to the system:
disarm the area, use the Unbypass a Point
(Command 00) function, send the RAM II unbypass
command, or execute an "Unbypass a Point" Sked.
When a point is bypassed because of a swinger
Swinger Bypass
condition, a
Default:
No
Selection:
Yes or No
Yes
Enable Swinger Bypass for this point.
No
Disable Swinger Bypass for this point.
Bosch Security Systems | 2/04 | 74-06145-000-D
Point Index
Restoral
should be YES for bypassable 24-hour points.
of 9 to D. 24-hour points do not show faults or bypasses when an arming command is
) or by a Sked programmed to arm the area.
report is sent.
Returnable
report is not sent when the point is unbypassed and it

P## Report Bypass at Occurrence

Generate a
Command Bypass
bypassed. This option should be enabled for all
bypassable 24-hour points. You may also elect to
report bypassed 24 –hour points at the time the area
Defer Bypass
is armed. See
Default:
No
Selection:
Yes or No
Send a
Yes
the time the point is bypassed.
Do not send
No
time the point is bypassed.
EN | 77
YES. Otherwise,
Returnable
is
Buz on Fault
and
report as soon as it is
report.
Command Bypass
report at
Command Bypass
at the