Table 31: BFSK/Relay Codes

BFSK Code

Trips Relay
1 =
73
2 =
74
3 =
75
4 =
76
5 =
77
6 =
78
7 =
79
8 =
80
Use these codes to activate relays on the D8129
OctoRelay or C8137 Transmitter Interface. You can
assign the same code to several points and effectively
provide a "summary zone" alarm output.
When the point goes into alarm the relay activates.
When the alarm is acknowledged and is no longer
scrolling in the command center display, the relay
resets. To reset the relay when a silent point trips,
enter a Passcode and press the [ENT] key, then a
Passcode and the [ESC] key.
Note:
The relay does not work for invisible points.
Two relays may activate when this point goes into
alarm if the Point Index used for this point is
programmed YES for

P### Point Text

Program Record Sheet
Default:
See
Selection:
Enter Alphabetic characters A to Z
in Capital Letters.
Note:
Period (.), comma (,), percent (%), parenthesis [()],
equal (=), greater/less than (< >), exclamation (!),
and colon (:) are not allowed.
Enter up to sixteen characters of text to describe the
point. This point text is displayed at command
centers (if the point is programmed as "visible") and
reported to the D6500 when transmitting in Modem
II format (if it is a reporting point).
Bosch Security Systems recommends you include
the point number in custom point text. This helps
the user, for example, when viewing events or
initiating bypasses, and can simplify troubleshooting.
Bosch Security Systems | 2/04 | 74-06145-000-D
Point Assignments
Relay Follows Point
.
8.2

Command 9

Defines how the Command 9 function operates.
User Cmd 9
Program this section if
User Interface module.
This function generates an
area where the command center is assigned. A new
report is generated each time it is activated, but only
one alarm appears in the alarm memory count at the
local area command centers. If this function is
activated in more than one area within the scope of
the command center, the alarm memory count is
increased.

Point Index

Default:
4
Selection:
Blank or 00 to 31
Point Index
Enter the
code used with Command 9.
0101
Point Index 00 (or blank) only works with
0101
Command 7 and Command 9. It is a silent,
0101
invisible, reporting point. Point Index 00
disables a normal point.
0101
Do NOT use a point index with Resettable
0101
programmed YES.
0101
Do NOT use a point index with Swinger
Bypass programmed YES.
BFSK Code
Default:
9
Selection:
Blank or 0 to 9
Use this entry to determine the point number
reported in BFSK when this point is tripped.
Normally, you only use this item when transmitting
reports to the central station in BFSK format.
0101
Command centers and local printers display
0101
the actual point number (1 to 135) not the
0101
BFSK report code.
Activating Relays: To activate a relay on the
D8129 OctoRelay or C8137 Transmitter Interface,
A# Command 9
see Relays
EN | 80