Replacing the Fan Drawer

Three fans are mounted in the Fan drawer, where the airflow is from right to left. Should
one of these fans fail as indicated by a Fan LED, you are required to replace the Fan drawer.
1
2
3
Warning!
The Fan drawer can be replaced when the RMX unit is ON, however a replacement drawer must be
inserted immediately. The temperature increase is detected by the system; when critical, a system
shutdown is initiated.
4
5
6
1-32
Slide in the replacement Power Supply unit.
Push the Power Supply unit firmly into the Backplane, making sure it is properly seated
in its slot.
Tighten the captive screws on the front panel of the RMX 2000 that secure the Power
Supply unit.
Turn ON the RMX 2000.
Unscrew the captive screws on the front panel of the RMX 2000 that secure the Fan
drawer.
Use the metal ejector levers to pull the Fan drawer out of its slot in the Backplane.
Carefully slide the Fan drawer out through the front panel.
Slide in the replacement Fan drawer.
Push the Fan drawer firmly into the Backplane, making sure it is properly seated in its
slot.
Tighten the captive screws on the front panel of the RMX 2000 that secure the Fan
drawer.