Chapter 6: Installing Summit Family Switches

Connecting the Ground Cable

WARNING!
Be sure to connect the chassis ground wire before you connect any power cables.
Be sure to disconnect the ground wire after you disconnect all power cables.
To connect the ground wire:
1 Verify that the DC circuit is de-energized.
2 Identify the grounding point on the front panel of the power supply (see
Figure 214: Connecting the Ground Wire
1 = Grounding point
2 = Ground wire
3 Insert an M3.5 screw (provided) through the ring terminal and into the grounding point on the
power supply.
4 Tighten the screw to 12.6 inch-pounds.
5 Connect the other end of the wire to a known reliable earth ground point at your site.

Connecting the Power Supply to the DC Source Voltage

The DC power connection at your facility must be made by a qualified electrician, following the
instructions in this section.
WARNING!
Always make sure that the DC circuit is de-energized before connecting or disconnecting the DC power
cables on the Summit X650 DC power supply.