Return To Non-Ice Build Operations Attach To Network Device Control; Operation - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

NOTE: The IceBuild steps donot o ccur if the chiller i sconfig-
ured andoperating asa lagor standby chillerfor lead/lag
operation and isactively being controlled byalead chiller T he
lead chiller c ommunicates
the
ICE BUILD
SET POINZ
the
desired
CHILLER
START/STOP
state,
and
the ACTIVE
DEMAND
LIMIT to the lag or standby chiller as required for
ice build, if configured
to do so.
START-UP/RECYCLE
OPERATION
-- If the chiller is not
running when ice build activates,
the HC III checks the fol-
lowing conditions,
based on the ICE BUILD
TERMINATION
value, to avoid starting the compressor
unnecessarily:
if ICE BUILD
TERMINATION
is set to the TEMP option
and the ENTERING
CHILLED
WATER
temperature
is
less than or equal to the ICE BUILD
SETPOINT;
if ICE BUILD
TERMINATION
is set to the CONTACTS
option and the ICE BUILD
CONTACT
is open;
if the ICE BUILD
TERMINATION
is set to the BOTH
(temperature
and contacts)
option
and the ENTERING
CHILLED
WATER
temperature
is less
than or equal
to the ICE BUILD
SETPOINT
and
the ICE BUILD
CONTACT
is open.
The
ICE BUILD
RECYCLE
on the OPTIONS
screen
determines
whether or not the chiller will go into an ice build
RECYCLE
mode.
If the ICE BUILD
RECYCLE
is set to DSABLE
(disable),
the HC III reverts to normal
(non-ice build) temperature
control
when
the ice build
function
is terminated
by
satisfying
one of the above conditions.
Once ice build is
terminated
in this manner,
it will not be reinitiated
until
the next ice build schedule
period begins.
If the ICE BUILD
RECYCLE
is set to ENABLE,
the PIC
III goes into an ICE BUILD
RECYCLE
mode, and the
chilled water pump relay remains
energized
to keep the
chilled water flowing
when the compressor
shuts down.
If the temperature
of the LEA1/ING
CHILLED
WATER
later increases
above
the ICE BUILD
SETPOINT
plus
half
the
RECYCLE
RESTART
DELTA
T value,
the
compressor
restarts,
controlling
the chilled
water/brine
temperature
to the ICE BUILD
SETPOINT.
TEMPERATURE
CONTROL
DURING
ICE BUILD
--
During ice build, the capacity control algorithm
shall use the
CONTROL
POINT
minus
5 F (-2.8
C)
for control
of
the LEAVING
CHILLED
WATER
temperature.
The
ECW
CONTROL
OPTION and any temperature
reset option shall be
ignored,
if enabled,
during
ice build.
Also, the following
control options will be ignored during ice build operation:
• ECW
CONTROL
OPTION
and
any temperature
reset
options
(confiigured
on TEMP_CTL
screen).
20
mA
DEMAND
LIMIT
OPT
(configured
on
RAMP_DEM
screen).
TERMINATION
OF ICE BUILD -- The ice build lhnction
terminates
under the following conditions:
1. Time Schedule --When
the current time on the ice build
time schedule (OCCPC02S)
is i,ot set as an ice build time
period.
2. Entering
Chilled Water Temperature
-- Ice build opera-
tion terminates,
based on temperature,
if the ICE BUILD
TERMINATION
paralneter
is set to 0 (TEMP),
the
ENTERING
CHILLED
WATER
temperature
is
less
than the ICE BUILD
SETPOINT.
and the ICE BUILD
RECYCLE
is set to DSABLE.
ff the ICE
BUILD
RECYCLE
OPTION
is
set to ENABLE,
a recycle
shutdown
occms
and
recycle
start-up
depends
on
the LEA1/ING
CHILLED
WATER
temperature
being
greater than the water/brine
CONTROL
POINT plus the
RESTART DELTA Ttemperature.
3. Remote Contacts/Ice
Level Input -- Ice build operation
terminates
when the ICE BUILD TERMINATION
param-
eter is set to 1 (CONTACTS)
and the ICE BUILD
CONTACTS
me open and the ICE BUILD
RECYCLE
is
set to DSABLE
(0). In this case,
the ICE BUILD
CONTACTS
provide
ice level termination
control.
The
contacts
m'e used to stop the ice build function when a
time period on the ice build schedule (OCCPC02S)
is set
for ice build operation.
The remote contacts
can still be
opened and closed to start and stop the chiller when a
specific time period on the ice build schedule is not set for
ice build.
4. Entering
Chilled
Water
Temperature
and ICE BUILD
Contacts --Ice
Build operation
terminates
when the ICE
BUILD
TERMINATION
parameter
is set to 2 (BOTH)
and the conditions
described
above in items 2 and 3 for
ENTERING
CHILLED
WATER
temperature
and ICE
BUILD CONTACTS
have occurred.
NOTE:
It is not possible
to override
file CHILLER
START/
STOP, CONTROL
POINE
and ACTIVE
DEMAND
LIMIT
variables
from CCN
devices
(with a priority
4 or greater)
during
the ice build
period.
Howevel:
a CCN
device
can
override these settings during 2-chiller lead/lag operation.
RETURN
TO NON-ICE
BUILD
OPERATIONS
-- Tile ice
build lunction forces the chiller to start, even if _dl other sched-
ules indicate that file chiller should stop. When
file ice build
lunction
terminates,
the chiller returns to normal temperatme
control and st_u't!stop schedule operation. The CHILLER START/
STOP and CONTROL
POINT return to normal operation. If the
CHILLER START/STOP
or CONTROL
POINT has been forced
(wifll a device of less than 4 priority) before file ice build func-
tion stmted, when the ice build lunction ends, the plevious forces
(of less than 4 priority) me not automatic_dly restored.
Attach to Network
Device Control -- _qle
Service
menu
includes
the ATTACH
TO
NETWORK
DEVICE
screen. From this screen, the operator can:
enter
the
time
schedule
number
(if
changed)
for
OCCPC03S,
as defined
in the NET_OPT
screen
attach
the ICVC
to any CCN device,
if the chiller
has
been connected
to a CCN
network.
This
may include
other PIC-controlled
chillers.
upgrade
software
Figure 25 shows the ATTACH
TO NETWORK
DEVICE
screen.
The LOCAL
parameter
is _dways the ICVC module
address of the chiller on which it is mounted.
Whenever
the
controller
identification
of the ICVC changes,
the change is
reflected
automatically
in the BUS and ADDRESS
columns
for the local device.
See Fig. 18. Default
addiess
for local
device is BUS 0 ADDRESS
1.
When
the ATFACH
TO NETWORK
DEVICE
screen is
accessed,
infomlation
can not be lead from the ICVC on any
device until one of the devices listed on that screen is attached.
The ICVC erases information
about the module to which it was
attached
to make room
for information
on another
device.
Therefore,
a CCN module must be attached when this screen is
entered.
To attach any CCN device, highlight it using the
softkey
and
press
the ]ATTACH]
sollkey.
The
message
"UPLOADING
TABLES,
PLEASE
WAIT'
displays.
The
ICVC
then uploads
the highlighted
device
or module.
If
the module addi'ess cannot be found, the message
"COMMU-
NICATION
FAILURE"
appems.
The ICVC then reverts back
to the ATTACH
TO DEVICE
screen. Try another device or
check the addiess
of the device that would not attach. The
upload
process
time for each CCN
module
is different.
In
gener_d, the uploading
process
takes 1 to 2 minutes.
Befole
leaving the ATTACH
TO NETWORK
DEVICE
screen, select
the LOCAL
device. Otherwise,
the ICVC will be unable to
display information
on the local chillel: