Shutdown Sequence; Automatic Soft Stop Amps Threshold; Chilled Water Recycle Mode - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

MACHINE SAFETIES,
EVAPORATOR PUMP
CONDENSER
WATER PUMP
WATER FLOW, CHILLED
WATER TEMP, GUIDE VANES
OIL PUMP,TOWER FAN CONTROL
OIL PRESSURE
COMPRESSOR,
COMPRESSOR ONTIME,
SERVICE ONTIME
15-MINUTE
START*TO-START
1-MINUTE
STOP-TO-START
*'TIME
ODE
3OM-
_RESSC
tUNNIN
I
!
II
F
G
O/A
A
--
START
INITIATED:
Pre-start
checks
are
made;
evaporator
pump
started,
B
--
Condenser
water pump started (5 seconds after A),
C
--
Water flows
verified
(30 seconds
to 5 minutes
maximum
after B).
Chilled
water
temperatures
checked
against
control
point,
Guide
vanes
checked
for closure,
Oil pump
started;
tower
fan control
enabled.
D
--
Oil pressure
verified (15 seconds
minimum, 300 seconds maximum
after C).
E
--
Compressor
motor starts;
compressor
ontime
and service
ontime
start, 15-minute
inhibit timer starts
(10 seconds
after D), total com-
pressor starts
advances
by one, and the number
of starts
over a
12-hour period advances
by one.
F
--
SHUTDOWN
INITIATED
-- Compressor
motor
stops; compressor
ontime and service ontime stop, and 1-minute inhibit timer starts.
G
--
Oil pump and evaporator
pumps deenergized
(60 seconds
after F).
Condenser
pump and tower fan control may continue
to operate
if
condenser
pressure
is high. Evaporator
pump may continue
if in
RECYCLE
mode.
O/A--
Restart permitted (both inhibit timers expired: minimum of 15 minutes
after E; minimum of 1 minute after F).
Fig. 27 -- Control
Sequence
Shutdown
Sequence--Chiller
shutdown
begins
if
any of the following occurs:
the STOP
button
is pressed
for at least one second
(the
alarm light blinks once to confirm
the stop command)
a recycle condition
is present (see Chilled
W_tter Recycle
Mode section)
the time schedule
has gone into unoccupied
mode
the chiller protective
limit has been reached and chiller is
in alarm
the start/stop
status is overridden
to stop from the CCN
network
or the [CVC
When
a stop signfd occurs, the shutdown
sequence
first
stops the compressor
by deactivating
the VFD output to the
motor
A status message
of "SHUTDOWN
IN PROGRESS,
COMPRESSOR
DEENERGIZED"
is displayed,
and
the
comptessor
ontime and service ontime stop. The guide vanes
are then brought to the closed position. The oil pump relay and
the chilled water/brine
pump telay shut down 60 seconds after
the compressor
stops. The condenser
water pump shuts down
at the same time if the ENTERING
CONDENSER
WATER
temperature
is greater
than or equal to 115 F (46.1 C) find
the
CONDENSER
REFRIG
TEMP
is greater
titan
the
CONDENSER
FREEZE
POINT
plus
5 F (-15.0
C). The
stop-to-statl
timer
now
begins
to
count
down.
If
the
statl-to-stmt
timer value is still greater than the value of the
start-to-stop
timet: then this time displays on the ICVC.
Certain conditions
that occur during shutdown
can change
this sequence.
[f the AVERAGE
LINE CURRENT
is greater
than 5%
alter
shutdown,
the oil pump
and chilled
water
pump
remain energized
and the alarm is displayed.
The
condenser
pump
shuts
down
when
the
CON-
DENSER
PRESSURE
is less than the COND
PRESS
OVERRIDE
threshold
minus
3.5 psi (24.1 kPa) and the
CONDENSER
REFRIG
TEMP is less than or equal to the
ENTERING
CONDENSER
WATER
temperature
plus
3° F (-1.6° C).
If the chiller
shuts down due to low refl'igerant
tempera-
ture, the chilled
water
pump continues
to run until the
LEAVING
(/HILLED
WATER temperature
is greater than
the CONTROL
POINTtemperature,
plus 5° F (2.8 ° C).
Automatic
Soft Stop Amps Threshold
-- The soft
stop fillips threshold
feature
closes
the guide
vanes of the
compressor
automaticfflly
if a non-recycle,
non-alarm
stop
signal occurs before the compressor
motor is deenergized.
Any time the compressor
is directed to STOP (except in the
cases of a fault or recycle
shutdown),
the guide vanes ate
directed to close, and the compressor
shuts off when any of the
following is true:
AVERAGE
LINE
CURRENT
(%)
drops
below
the
SOFT STOP AMPS THRESHOLD
ACTUAL
GUIDE VANE POSITION
drops below 4%
4 minutes
have elapsed
the STOP button
is pressed twice
If file chiller enters an alarm state or if the compressor
enters
a RECYCLE
mode, the compressor
deenergizes
immediately.
To activate the soft stop amps threshold feature, scroll to the
bottom
of
OPTIONS
screen
on
the
[CVC.
Use
the
[INCREASE]
or [DECREASE[
softkey to set the SOFT STOP
AMPS
THRESHOLD
parmneter
to the percent
of amps at
which the motor will shut down. The default setting is 100%
alnps (no soft stop). The range is 40 to 100%.
When the soft stop amps threshold feature is being applied,
a status message,
"SHUTDOWN
IN PROGRESS,
COM-
PRESSOR
UNLOADING"
displays on the ICVC.
The soft stop amps threshold function can be terminated
and
the compressor
motor deenergized
immediately
by depressing
the STOP button twice.
Chilled
Water Recycle
Mode--
The
chiller
may
cycle off and wait until the load increases
to restart when the
compressor
is running
in a lightly loaded
condition.
This
cycling
is norlnal and is known as "recycle."
A recycle shut-
down is initiated when any of the following conditions
are true:
LEA1/ING
CHILLED
WATER
temperature
(or ENTER-
ING
CHILLED
WATER
temperature,
if
the
ECW
CONTROL
OPTION
is enabled)
is more
than
5 ° F
(2.8 ° C) below the CONTROL
POINT.
LEAI/ING
CHILLED
WATER
temperature
(or ENTER-
ING
CHILLED
WATER
temperature,
if
the
ECW
CONTROL
OPTION
is enabled)
is below the CONTROL
POINT.
and the chilled
water temperature
difference
is
less
than
the
(RECYCLE
CONTROL)
SHUTDOWN
DELTA
T (configured
in the EQUIPMENT
SERVICE/
SETUPI
table).
the LEA1/ING
(/HILLED
WATER temperature
is within
3 ° F (1.7 ° C) of the EI/AP REFRIG
TRIPPOINT.
NOTE:
Recycle
shutdown
will not occur if the CONTROL
POINT has been modified (e.g., by a chilled water reset input)
within the previous 5 minutes of operation.
Also, chilled water recycle logic does not apply to Ice Build
operation (refer to page 46).
When the chiller is in RECYCLE
mode, the chilled water
pump relay remains energized
so the chilled water temperatute
can be monitored
for increasing
load. The recycle control uses
RESTART
DELTA T to check when the compressor
should be
restarted.
This
is an
opettltor-configured
function
which
defaults to 5 ° F (2.8 ° C). This value can be viewed or modified
51