Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 12

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

INTERNATIONAL
CHILLER
VISUAL
CONTROLLER
(ICVC)
-- The ICVC is the "brain" of the PIC HI. This mod-
ule contains
all the operating
software
needed to control the
chillel: The ICVC is mounted to the control panel (Fig. 9) and
is the input center
for all local chiller set points,
schedules,
configurable
functions,
and options.
The [CVC has a stop
button,
an alarm
light, four bnttons
for logic inputs, and a
backlight
display. The backlight
will automatically
turn off
after 15 minutes
of non-use.
The lhnctions
of the four buttons
or "softkeys"
me menu driven and are shown on the display
directly above the softkeys.
The viewing angle of the ICVC can be adjusted for opti-
mum viewing. Remove the 2 bolts connecting
the control panel
to the brackets attached to the coolec Place them in one of the
holes to pivot the control panel forw_ud to backward
to change
the viewing angle. See Fig. 9. To change the contrast of the
display, access the adjustment
on the back of the ICVC. See
Fig. 9.
The ICVC features 4 factory progrmnmed
languages:
English (default)
Chinese
Japanese
Kolean
NOTE:
Plessing
any one of the four softkey
buttons
will acti-
vate
the
backlight
display
without
implementing
a softkey
function.
The [CVC
may
be identified
by viewing
the back
of the plate
on which
the display
is mounted.
(Open
the control
panel
door
to view.)
Note
any of the following
distinguishing
features
in
Table
2.
Table 2 -- Identification
Features of the ICVC
COLOR
CEPL No.
CONTROLLER
OF
(hardware)
PLATE
ICVC
Metallic
CEPL
130445-02
SOFTWARE
CESR
131350-0X
OTHER
MARKINGS
"PIC IIr'
Marking
on back
of green
circuit
board
MOTOR TEMPERATURE
OIL RECLAIM
SIGHT GLASS_
COMPRESSOR
OIL DISCHARGE
PRESSURE
CABLE
BEARING TEMPERATURE
CABLE
AND DIFFUSER ACTUATOR
CABLE (FRAME 4 & 5
COMPRESSOR
ONLY)
COMPRESSOR
OIL SUMP
COMPRESSOR
OIL SUMP
GUIDE
ACTUATOR
CABLE
CABLE FROM
CONTROL
PANEL
COMPRESSOR
DISCHARGE
TEMPERATURE
SENSOR
CABLE
HIGH PRESSURE
SWITCH
LOCATION
OIL COOLER
THERMOSTATIC
EXPANSION
VALVE (TXV)
OIL COOLER THERMOSTATIC
EXPANSION
VALVE (TXV) BULB
OIL HEATER TERMINAL
BOX
Fig. 8 -- 19XRV Compressor Controls and Sensor Locations
12