Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 90

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Table 16 -- Alarm and Alert Messages (cont)
J. CHILLER
ALERTS
(cont)
ICVC FAULT
PRIMARY
SECONDARY
PRIMARY CAUSE
ADDITIONAL
CAUSE/REMEDY
STATE
MESSAGE
MESSAGE
151
CONDENSER
PUMP RELAY
151_High
Condenser
Pres-
Check sensor wiring and accuracy.
PRESSURE
ALERT
ENERGIZED
sure [VALUE]: Pump Ener-
Check condenser flow and water temperature.
gized to Reduce Pressure.
Check for fouled tubes.
This alarm is not caused by the High Pressure
Switch.
152
RECYCLE ALERT
EXCESSIVE RECYCLE
152_Excessive
recycle
Chiller load is too low to keep compressor
on
STARTS
starts,
line and there has been more than 5 starts in
4 hours.
Increase chiller load, adjust hot gas bypass,
increase RECYCLE RESTART DELTA T from
SETUP1 Screen.
153
no message:
no message; ALERT only
153_Lead/Lag
Disabled-
Illegal chiller address configuration
in Lead/Lag
ALERT
Config: Duplicate Chiller
screen. Both chillers require a different address.
only
Address.
154
POTENTIAL
COND PRESS/TEMP
154_Condenser
freeze up
The condenser pressure transducer is reading a
FREEZE=UP
TOO LOW
)revention.
3ressure that could freeze the condenser tubes.
Check for condenser refrigerant leaks.
Check fluid temperature.
Check sensor wiring and accuracy.
Place the chiller in PUMPDOWN
mode if the
vessel is evacuated.
155
OPTION SENSOR
REMOTE RESET
155-_Sensor
Fault/Option
Check sensor resistance or voltage drop.
FAULT
SENSOR
Disabled: Remote Reset
Check for proper wiring to CCM connector J4.
Sensor.
156
OPTION SENSOR
AUTO CHILLED WATER
156_-_Sensor Fault/Option
Check sensor resistance or voltage drop.
FAULT
RESET
Disabled: Auto Chilled Water
Check for proper wiring to CCM connector J5.
Reset.
157
OPTION SENSOR
AUTO DEMAND LIMIT
157-_Sensor
Fault/Option
Check sensor resistance or voltage drop.
FAULT
INPUT
Disabled: Auto Demand Limit
Check for proper wiring to CCM connector J5.
Input.
158
SENSOR ALERT
SPARE TEMPERATURE
158_-_Spare Temperature
1
#1
[VALUE] exceeded limit of
[LIMIT]*.
159
SENSOR ALERT
SPARE TEMPERATURE
159_Spare
Temperature 2
#2
[VALUE] exceeded limit of
[LIMIT]*.
161
LOSS OF
WITH WSM
161_-_WSM Cool Source --
COMMUNICATION
Loss of Communication.
162
SENSOR ALERT
EVAPORATOR
APPROACH
162-_ Evaporator Approach
[VALUE] Exceeded Limit of
[LIMIT]*.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #1 Limit in SETUP1 screen.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #2 Limit in SETUP1 screen.
Check settings in WSMDEFME
screen.
Check CCN communications
link with WSM
(Water System Manager) Module.
Check Supervisory
Part of WSM.
Check that refrigerant charge level is adequate,
waterbox division plate gaskets are sealing,
evaporator tubes are not fouled and that oil
reclaim system is working.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check Evap Approach Alert setting in SETUP1
screen.
Check sensors resistance or voltage drop.
Check for proper wiring.
Check Cond Approach Alert setting in SETUP1
screen.
Check for noncondensable
gas in the
condenser.
Check that the condenser tubes are not fouled.
Actual VFD Speed on COMPRESS screen must
be at least 90% of Target VFD Speed.
163
SENSOR ALERT
CONDENSER
APPROACH
163-_Condenser
Approach
[VALUE] Exceeded Limit of
[LIMIT]*.
164
VFD SPEED ALERT
LOW VFD SPEED
164_Actual
VFD Speed
exceeded limit of Target VFD
Speed -10%.
165
AUTORESTART
LOW DC BUS VOLTAGE
165_Low
DC Bus Voltage:
Verify phase to phase and phase to ground line
PENDING
[VALUE] Exceeded Limit of
voltage.
[LIMIT]*.
166
AUTORESTART
HIGH DC BUS VOLTAGE
166_High
DC Bus Voltage:
Verify phase to phase and phase to ground line
PENDING
[VALUE] Exceeded Limit of
voltage. Monitor AC line for high transient volt-
[LIMIT]*.
age conditions.
167
SYSTEM ALERT
HIGH DISCHARGE
TEMP
167_Comp
Discharge Temp
Check sensor resistance or voltage drop.
[VALUE] exceeded limit of
Check for proper wiring.
[LIMIT]*.
Check for excessive starts.
Check Comp Discharge Alert setting in SETUP1
screen.
168
SENSOR ALERT
HUMIDITY SENSOR
168-_Sensor
Fault: Check
Check humidity sensor wiring on CCM connec-
INPUT
Humidity Sensor Input Sensor. tots J3 and J5.
Check Humidity Sensor Input in Controls Test.
*[LIMIT] is shown on the ICVC as the temperature,
pressure, volta e, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
90