NOTES:
I
GENERAL
1,0 VFD SHALL BE DESIGNED AND MANUFACTURED
IN ACCORDANCE
WITH
CARRIER ENGINEERING REQUIREMENT Z-420o
1,1
ALL FIELD-SUPPUED CONDUCTORS, DEVICES AND 'THE FIELD-INSTALLATION
WIRING, TI'3:_MINAIlON GF CONDUCTORS AND DEVICES, MUS'f 8E IN COMPUANCE
WITH ALL APPUCABLE
CODES AND JOB SPECIFICATION&
1.2 THE ROUTING OF FIELD-INS'[ALLEDCONDUIT AND CONDUCTORS
AND THE LOCA]ION
OF FIELD-INSTALLED DEVICES, MUST NOT INTERFERE WITH EQUIPMENT ACCESS
OR THE READING. AOdUSIlNG OR SERVICING OF ANY COMPONENT,
1,3 EQUIPMENT INSIALLATION AND ALL STARIINO AND CONTROL DEVICES. MUST
COMPLY
_lll DEIAILS IN EQUIPMENT SUBMITTAL DRA_NOS
AND UTERATURE.
1,4 CONrACIS
AND S_TCHES
ARE SHOWN
IN THE POSITION IHEY WOULD
ASSUME
WITH THE CIRCUIT DE-ENERGIZED
AND THE CHILLER SHUII]OYvN.
1,5 NARNING - DO NOT USE ALUMINUM CONDUCTORS,
POWER
_RING
TO VFD
2,0
PROVIDE A LOCAL MEANS
OF DISODNNEGTINO POWER
TO VFD, PROVIDE SHORT
CIRCUIT PROTECTION FOR THE CHILLER AND INIERCONNECTING WIRE AT THE
BRANCH FEEDER. IHE SHOR'[ CIRCUIT PROfE'_:TION SHALL BE FUSED TYPE
OR EQUiVALEN'f CIRCUIT BREAKDR PER SHEEI 3 OF 4 OF THIS DOCUMEN'f.
Z,1 METAL CONDUII MUST BE USED FGR IHE POI_ER WIRES, FROVI VFD TO BRANCH
FEEDER.
2,2
UNE S@E
POWER CONDUCTOR
RATING MUST
MEET VFD NAMEPLATE
VOLTAGE
AND CHILLER FULL LOAD AMPS
(MINIMUM CIRCUIT AMPACITY),
2,3
UNE LUG ADAPTORS
ARE REQUIRED AT INSTALLATION. MINIMUM QUANTITY
(# CONDUCTORS)
AND SIZE (CONDUCTOR
RANGE)
CABLES PER PHASE
AS FI_I_I.OWS:
CONTROL
_RI N(3
&O
FIELD SUPPLIED CONTROL
CONDUCTORS
TO BE AT LEAST 18 A_
OR LAROEP,.
3.1 ICE BUILD START/ERMINATE
DEVICE CONTACTS, REMOTE
START/STOP
DEVICE CONTACTS
AND SPARE
SAFELY DEVICE CONTAC:TS_ (DEVICES NOI SUPPUED
BY CARRIER],
MUST HAVE
24VAC RATING. MAX CURRENT
IS BOrnA. NOMINAL CURRENT
IS 10mA.
SWI'[CHES WITH C43LI) PLATED BIFURCATED C:ONIAC'ISARE RECX3MMENDED.
3.2 REMOVE
,.LIMPERWIRE BETWEEN
TBI-Ig AND "fBI-20 BEFORE CDNNECI]N_
AUXILLIARY
SAFETIES BETV_
THESE TERMINALS.
3,_
TME VF'D CONTACT
OUTPUTS
CAN CONTROL
LOADS
(VA)
FOR COOLER AND
FOR CONDENSER
PUMP,
TOWER FAN MOTOR CONTACTOR
COIL AND
ALARM
ANNUNCIATOR
DEVICES IS RATED 5 AMPS
AT 115VAC
UP TO 3 AMPS
AT
277VAC.
CONTROL
WIRING REOUIRED FOR CARRIER
TO START PUMPS
AND
TOWER
FAN
MOTORS MUST BE PROVIDED
TO ASSURE
MACHINE
PROTECTION,
IF PRIMARY
PUMP
AND
TOWER FAN MOTOR CONTROL IS BY OTHER MEANS. ALSO PROVIDE
A
PARALLEL
MEANS
FOR DDNTROL BY CARRIER.
DD NOT USE STARTER
CONTROL
TRANSFORMER
AS THE POWER SOURCE
FOR CONTACTOR
COIL, ACTUATOR
MOTOR
DR ANT
OTHER
LOADS.
3.4 DO NOT ROUTE CONTROL
WIRINI_ CARRYING 3DV OR LESS WIIHIN A CONDUIT "NHICH
HAS WIRES 'CARRYING 50V OR HIGHER OR ALONG SIDE WIRES CARR'fING 50V OR HIGHER,
3.5
SPARE
$-20mA
OUTPUT
SIGNAL
IS DESIGNED
FOR CONTROLLERS
WITH A
NON--GROUNDEO
4-20mA
INPUT SIGNAL
AND
A MAXIMUM
INPUT IMPEDANCE
OF 500 OHMS.
3.6
REMOVE JUMPER
WIRE TB1/19
TO TB1/20
IF INSTALLING
SPARE
SAFETY" CONTACT.
VFD
STANDARD 65KAIC
LUG CAPACITY (PER PHASE)
OP_ONAL
IOOKAIC LUG CAPACITY (PER PHASE)
MAX INPUT
AMPS.
# CONDUCTORS
CONDUCTOR RANGE
# CONDUCTORS
CONDUCTOR RANGE
405A
3
3/0
-
500MCM
2
40D - 500MCM
608A
3
3/0-
500MCM
3
3/0
-
400MCM
2.4- COMPRESSOR
MOTOR
AND CONTROLS
MUST BE GROUND[I) BY USING EGUIPM[NT
GROUNDING
LUGS PROVIDED INSIDE UNIT MOUNTED
VFD ENCLOSURE,
Fig. 54 -- 19XRV Field Wiring