Table 16 -- Alarm and Alert Messages (cont)
I. CHILLER PROTECTIVE
LIMIT FAULTS (cont)
ICVC FAULT
STATE
259
282
283
284
285
286
PRIMARY
MESSAGE
PROTECTIVE
LIMIT
PROTECTIVE
LIMIT
PROTECTIVE
LIMIT
VFD GATEWAY
VFD GATEWAY
PROTECTIVE
LIMIT
SECONDARY
MESSAGE
CCN OVERRIDE
STOP
INVALID VFD CONFIG
INVALID VFD CONFIG
COMPATIBILITY
CONFLICT
COMPATIBILITY
CONFLICT
INVERTER
OVERCURRENT
PRIMARY CAUSE
259_CCN
Emergency/
Override Stop.
282-+Line
Frequency
[VALUE] Exceeded Configura-
tion Range.
283_Compressor
100%
Speed Config Ranges: 50=Hz
45-52; 60 Hz=55-62.
284_VFD
Gateway Compati-
bility Conflict: Check VFG/
VFD Versions.
285-_VFD
Gateway Compati-
bility Conflict: Check VFG/
ICVC Versions.
286_lnverter
Overcurrent
Fault: Check VFD Status.
ADDITIONAL
CAUSE/REMEDY
CCN has signaled the chiller to stop.This fault
must be manually reset from the default screen
of the ICVC.
LINE FREQUENCY
in POWER screen must be
maintained between 45-52 Hz if LINE
FREQ=60Hz?
is set to NO(50 Hz). LINE FRE-
QUENCY must be maintained between
55-62 Hz if LINE FREQ=60Hz?
is set to YES
(60 Hz).
COMPRESSOR
100% SPEED in VFD CONF
screen must be set between 45-52 Hz [{ LINE
FREQ=60Hz?
is set to NO(50 Hz). COMPRES-
SOR 100% SPEED must be set between
55-62 Hz if LINE FREQ=60Hz?
is set to YES
(60 Hz).
VFD Gateway and VFD software versions are
not compatible. Call Carrier Service.
VFD Gateway and ICVC software versions are
not compatible. Call Carrier Service.
Check for high entering water temperature or
low condenser water flow.
Check current settings in VFD CONF screen.
*[LIMIT] is shown on the ICVC as the temperature,
pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
J. CHILLER ALERTS
ICVC FAULT
STATE
140
141
142
143
144
145
146
147
PRIMARY
MESSAGE
SENSOR ALERT
SENSOR ALERT
LOW OIL
PRESSURE
ALERT
AUTORESTART
PENDING
AUTORESTART
PENDING
AUTORESTART
PENDING
AUTORESTART
PENDING
AUTORESTART
PENDING
SECONDARY
MESSAGE
LEAVING COND WATER
TEMP
ENTERING COND WATER
TEMP
CHECKOILFI_ER
LINECURRENT
IMBALANCE
LINEVOLTAGE
DROPOUT
HIGH LINE VOLTAGE
LOW LINE VOLTAGE
VFD MODULE RESET
148
AUTORESTART
POWER LOSS
PENDING
149
SENSOR ALERT
HIGH DISCHARGE
TEMP
150
SENSOR ALERT
HIGH BEARING
TEMPERATURE
PRIMARY CAUSE
140-_Sensor
Fault: Check
Leaving Cond Water Sensor.
141_Sensor
Fault: Check
Entering Cond Water Sensor.
142_Low
Oil Pressure Alert.
Check Oil Filter.
143-_Line Current Imbal-
ance: Check VFD Fault His-
tory for Values.
144-+Single
Cycle Line
Voltage Dropout.
145_High
Percent Line
Voltage [VALUE].
146_Low
Percent Line
Voltage [VALUE].
147->VFD Module Power-On
Reset When Running.
148_Control
Power-Loss
When Running.
149_Comp
Discharge Temp
[VALUE] Exceeded Limit of
[LIMIT]*.
150_Comp
Thrust Brg Temp
[VALUE] exceeded limit of
[LIMIT]*.
ADDITIONAL
CAUSE/REMEDY
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.
Power loss has been detected in any phase.
Chiller automatically
restarting.
A drop in line voltage has been detected within
2 voltage cycles.
Chiller automatically
restarting
if Auto Restart
is
enabled in OPTIONS screen.
Check phase
to phase
and phase
to ground line
)ower.
Check phase
to phase
and phase
to ground line
)ower.
VFD Module has detected a hardware fault due
to electrical noise, power loss or software and
has reset. Chiller automatically
restarting.
Check for power loss and sources of electro-
magnetic
interference.
Check 24 vac control power supply to ICVC.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper condenser flow and
temperature.
Check for high lift or low load.
Check for fouled tubes or noncondensables
in
the chiller.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil level and oil level.
*[LIMIT] is shown on the ICVC as the temperature,
pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
89