Maintenance; Properties; Refrigerant - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

DISTILLING THE REFRIGERANT
1. Transfer the refligerant flom the chiller to the pumpout
storage tank as described in the Transfer the Refligerant
from Chiller to Pumpout Storage Tank section.
2. Equalize the refl'igerant pressure.
a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, and
10, and close chiller charging valve 7; open chiller
isolation valve 11 and any other chiller isolation
valves, if present.
c. Open pumpout and storage tank valves 3 and 6;
open chiller valves la and lb.
VALVE
la
lb
2
3
4
5
6
7
10
11
CONDITION
C
C
C
C
C
d.
Gradually
crack
open
valve
5 to increase
chiller
pressure to 35 psig (241 kPa). Slowly feed refriger-
ant to prevent freeze-up.
e.
Open valve 5 fully after the chiller
pressure
rises
above the freezing
point of the refrigerant.
Let the
storage tank and chiller pressure equalize.
3. Transfer remaining
refrigerant.
a.
Close valve 3.
b. Open valve 2.
c.
Turn on pumpout
condenser
water.
d.
Run the pumpout
compressor
until the storage tank
pressure reaches
5 psig (34 kPa), 18 in. Hg vacuum
(41 kPa absolute)
in Manual
or Automatic
mode.
e.
Turn off the pumpout
compressor.
f.
Close valves
la, lb, 2, 5, and 6.
g.
Turn off pumpout
condenser
water.
VALVE
la
lb
2
3
4
5
6
7
10 11
CONDITION
C
C
C
C
C
C
C
C
C
4. Drain the contaminants
from the bottom of the storage
tank into a containel:
Dispose of contaminants
safely.
GENERAL
MAINTENANCE
Refrigerant
Properties
-- The standard refrigerant for
the 19XRV chiller is HFC-134a. At normal atmospheric
pressure, HFC-134a refrigerant will boil at -14 F (-25 C) and
must, therefore, be kept in pressurized containel.s or storage
tanks. The refrigerant is practically odorless when mixed with
air and is noncombustible at atmospheric pressure. Read the
Material Safety Data Sheet and the latest ASHRAE Safety
Guide for Mechanical Refrigeration to learn more about safe
handling of this refrigerant.
Refrigerant HFC-134a will dissolve oil and some nonme-
tallic materials, dq the skin, and, in heavy concentrations,
may displace enough oxygen to cause asphyxiation. When
handling this refrigerant, protect the hands and eyes and
avoid breathing fumes.
Adding
Refrigerant--Follow
the
procedures
de-
scribed in Trim Refrigerant
Charge section, page 75.
Always
use
the
compressor
pumpdown
function
in the
Control
Test table
to turn on the cooler
pump
and lock out
the compressor
when
transfen'ing
refrigerant.
Liquid
reflig-
emnt
may
flash
into a gas and
cause
water
in the
heater
exchanger
tubes
to freeze
when
the
chiller
pressure
is
below
35 psig (241 kPa)
for HFC-134a,
resulting
in equip-
ment damage.
Removing Refrigerant
-- If the optional pumpout sys-
tem is used, the 19XRV refrigerant charge may be transferred
to a pumpout storage tank or to the chiller condenser or cooler
vessels. Follow the procedures in the Pumpout and Refrigerant
Transfer Procedmes section when transferringrefrigerant from
one vessel to another:
Adjusting
the Refrigerant
Charge -- If the addi-
tion
or removal
of refrigerant
is required
to improve
chiller
performance,
follow
the procedures
given
under
the Trim
Refrigerant
Chmge section, page 75.
Refrigerant Leak Testing
--
Because
HFC-134a
re-
frigerant
is above atmospheric
pressure at room temperature,
leak testing can be performed
with refrigerant
in the chillel:
Use an electronic
halide leak detector, soap bubble solution, or
ultrasonic leak detectol: Ensure that the room is well ventilated
and free from concentration
of refrigerant
to keep false read-
ings to a minimum.
Before making aW necessguy repairs to a
leak, transfer all refrigerant from the leaking vessel.
Leak Rate
--
It is recommended
by ASHRAE
that chillers
be taken off line immediately
and repaired if the refrigerant
leak rate for the entire chiller is more than 10% of the operating
refrigerant charge per yegu:
In addition,
Carrier recommends
that leaks totalling
less
than the above rate but more than a rate of 0.1% of the total
chguge per yegu should be lepaired during annu_d maintenance
or whenever
the refrigerant
is transferred
for other service
work.
Test After Service,
Repair,
or Major
Leak-
If
all the refrigerant
has been lost or if the chiller has been opened
for service, the chiller or the affected vessels must be pressure
tested and leak tested. Refer to the Leak Test Chiller section to
perform a leak test.
HFC-134a
refrigerant
should
not be mixed
with air or
oxygen
and pressurized
for leak testing. In general,
this
refrigerant
should not be present with high concentrations
of air or oxygen above atmospheric
pressures, because the
mixture
can undergo
combustion,
which
could result in
serious personal injury or death.
TESTING WITH REFRIGERANT TRACER -- Use an en-
vironmentally acceptable refrigerant as a tracer for leak test
procedures. Use dry nitrogen to raise the machine pressure to
leak testing levels.
TESTING WITHOUT REFRIGERANT TRACER -- Anoth-
er method of leak testing is to pressurize with nitrogen only and
to use a soap bubble solution or an ultrasonic leak detector to
determine if leaks are present.
74

Advertisement

Table of Contents
loading

Table of Contents