Icvc Operation And Menus; General; Alarms And Alerts; Icvc Menu Items - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

ICVC Operation
and Menus
(Fig. 14-20)
GENERAL
The [CVC
display
automatically
reverts
to the default
screen after 15 minutes
if no softkey activity
takes place
and if the chiller is not in the pump down mode (Fig. 14).
If a screen other than the default
screen is displayed
on
the ICVC,
the name
of that
screen
is in the top line
(Fig. 15).
The ICVC
may be set to display
either
English
or SI
units. Use the ICVC configuration
screen (accessed
from
the Service
menu)
to change
the units.
See the Service
Operation
section,
page 48.
NOTE: The date format on the default screen is MM-DD-YY
for English units and DD-MM-YY
for SI metric units.
Local Operation
-- In LOCAL
mode the PIC III accepts
commands
fiom the ICVC only and uses the local time
occupancy
schedule
to determine
chiller
start and stop
times.
The PIC III can be placed
in the local operating
mode
by pressing
the LOCAL
softkey.
When
RUN
STATUS is READY.
the chiller will attempt
to start up.
CCN
Opelation
--In
CCN
mode
the PIC III accepts
input from any CCN interface
or module
(with the proper
authority)
as well as from the local ICVC.
The PIC III
uses the CCN
time occupancy
schedule
to determine
start and stop times.
The PIC III can be placed
in the
local
operating
mode
by pressing
the CCN
softkey.
When RUN STATUS
is READY.
the chiller
will attempt
to start up.
OFF --
The control
is in OFF mode when
neither
the
LOCAL
nor CCN
softkey
cue is highlighted.
Pressing
the STOP
key or an alarm
will place the control
in this
mode.
The
PIC III control
must
be in this mode
for
certain operations,
such as performing
a Control
Test or
accessing
VFD Configuration
parameters.
ALARMS
AND ALERTS
-- An altu'm shuts down the com-
pressor
An alert does not shut down the compressol:
but it
notifies the operator that an unusual condition has occurred. An
alarm (*) or alert (!) is indicated
on the STATUS screens on the
far right field of the ICVC display screen.
Alarms are indicated when the control center _darm light (!)
flashes. The primtuy alarm message is displayed on the default
screen. An additional,
secondary
message
and troubleshooting
information
are sent to the ALARM HISTORY
table.
When an alarm is detected, the ICVC default screen will
fieeze (stop up&_ting) at the time of alarm. The freeze enables
the operator to view the chiller conditions
at the time of alarm.
The STATUS tables will show the updated information. Once
all aimms have been cleared
(by pressing the _
soft-
key), the default ICVC screen will return to normal operation.
An alarm condition
must be rectified before a RESET
will
be processed.
However.
an _dert will clear automatically
as
soon as the associated
condition is rectified.
ICVC MENU
ITEMS -- To perform
any of the operations
described
below, the PIC III must be powered
up and have
successfully
completed
its self test. The self test takes place
automatically,
after power-up.
Press the _
softkey to view the list of menu struc-
tures:
_,
[SCHEDULE],
LSETPOINT],
and
[SERVICEI.
The STATUS menu allows
viewing
and limited
calibra-
tion or modification
of control points and sensors,
relays
and contacts,
and the options
board.
PRIMARY STATUS
STATUS
MESSAGE
(ILLUMINATED
WHEN POWER ON)
• BLINKS CONTINUOUSLY
ON FOR AN ALARM
• BLINKS ONCE
TO
CONFIRM
A STOP
COMPRESSOR
DATE
ON TIME
• HOLD FOR ONE
SECOND
TO STOP
mmmm
/
/
SOFT KEYS
EACH KEY'S
FUNCTION
IS
MENU
DEFINED
BY THE MENU
DESCRIPTION
LINE
ON MENU
LINE ABOVE
Fig. 14--
ICVC Default
Screen
DEVICE NAME
SCREEN NAME
mmm
Fig. 15 -- ICVC Service Screen
The SCHEDULE
menu allows viewing and modification
of the local and CCN time schedules
and Ice Build time
schedules.
The SETPOINT
menu allows set point adjustments,
such
as the entering
chilled water and leaving chilled water set
points.
The SERVICE
menu
can be used to view
or modify
information
on the Alarm
History, Control
Test, Control
Algorithm
Status,
Equipment
Configuration,
VFD Con-
figuration
data,
Equipment
Service,
Time
and
Date,
Attach to Network
Device,
Log Out of Network
Device,
and ICVC Configuration
screens.
For more
information
on the menu
structures,
refer to
Fig. 17.
Press the softkey that corresponds
to the menu structure to
be
viewed:
_
ISCHEDULEI,[SE OINTI, or
[SERVICE].
To view or change parmneters
within any of these
menu structures,
use the _
and [PREVIOUS[
softkeys
to scroll down to the desired item or table. Use the
softkey to select that item. The softkey choices that appear next
depend on the selected table or menu. The softkey choices and
their functions are described below.
BASIC ICVC OPERATIONS
(Using the Softkeys) -- To per-
form any of the operations
described below, the PIC III must be
powered up and have successfully
completed
its self test.
16

Advertisement

Table of Contents
loading