Starting Equipment; Unit-Mounted Vfd - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

REAR MOTOR
OIL SUPPLY
TO
FORWARD
HIGH
SPEED
BEARING
I
(
FWD MOTOR
LABYRINTH
GAS
LINE
MOTOR
COOLING
LINE
PRESSURE
TRANSDUCER
OIL
ISOLATION
PUMP
VALVES
OIL
OIL
HEATER
COOLER
OILPUMP
MOTOR
SIGHT
GLASS
FILTER
ISOLATION
VALVE
GLASS
ISOLATION
VALVE
Fig. 4-
Lubrication System
t
LINE
STARTING
EQUIPMENT
All 19XRV units am equipped
with a VFD to operate the
centrifugal hermetic compressor
motoc A power panel controls
the oil pump, and various auxiliary
equipment.
The VFD and
power
panel
m'e the main
field wiring
interfaces
for the
contractol: The VFDs are mounted directly on the chillel:
Three separate circuit breakers ale inside the st_utel: Circuit
breaker CBI is the VFD circuit breaker
The disconnect
switch
on the stmler fiont cover is connected
to fills breakel: Circuit
breaker CBI supplies power to the VH).
The main circuit breaker (CBI) on the front of the starter
disconnects
the main VFD current only. Power is still ener-
gized
for the other
circuits.
Two more circuit
breakers
inside the VH) must be turned off to disconnect
power to
the oil pump, PIC III controls, and oil heatel:
Circuit breaker
CB2 supplies
l15-v power to the control
panel, oil heater, and portions of the starter controls.
Circuit breaker CB3 supplies power at line voltage to the oil
pump. Both CB2 and CB3 are wired in pm'allel with CBI
so
that power is supplied to them if the CBI disconnect
is open.
Do not touch the power wiring or motor terminals while
voltage is present, or serious injury will result.
Unit-Mounted
VFD
--
The 19XRV chiller is equipped
with a variable frequency
drive motor controller
mounted
on
file condensel: See Fig. 5-7. This VFD is used wifll low voltage
motors between 380 and 480 wtc. It reduces the starting current
inrush by controlling
the voltage and fiequency
to the compres-
sor motol: Once the motor has accelerated
to minimum
speed
the PIC IIl modulates
the compressor
speed and guide vane
position
to control
chilled water temperature.
The VFD
is
further explained
in the Controls
section and Troubleshooting
Guide section, pages 11 and 79.
Operational
p_uameters and fault codes are displayed rela-
tive to the drive. Refer to specific (hive literatme
along with
troubleshooting
sections. The display is _dso the interface
for
entering specific chiller operational
p_u'ametel_. These ptuame-
ters have been preprogrammed
at the factory. An adhesive
backed label on the inside of the drive has been provided
for
verification
of the specific job paralneters.
See Initial St_ut-Up
Checklist section for details.