Control Modules; Inputs; Outputs - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Control
Modules
Turn controller power off before servicing controls. This
ensures safety and prevents &image to the controllec
The ICVC and CCM modules perform continuous
diagnos-
tic evaluations
of the hmdware
to determine
its condition.
Proper
operation
of all modules
is indicated
by LEDs
(light-emitting
diodes) located on the circuit board of the ICVC
and CCM.
There is one green LED located on the CCM board, and one
red LED located on the ICVC and CCM boards respectively.
RED LED (Labeled
as STAT) --If
the red LED:
Blinks continuously
at a 2-second
interval,
the module
is
operating
properly
Is lit continuously,
there
is a problem
that
requires
replacing
the module
Is off continuously,
the power should be checked
Blinks
3 times
per second,
a software
error
has been
discoveled
and the module
must be replaced
If there is no input powel, check the luses and circuit breaker
If the fuse is good, check for a shorted secondary of the trans-
former or. if power is present to the module, replace the module.
GREED LED (Labeled
as COM)--
These
LEDs
indicate
the communication
status between different
paris of the con-
troller and the network modules and should blink continuously.
Notes
on Module
Operation
1. The chiller
operator
monitors
and modifies
configura-
tions in the microprocessor
by using the 4 softkeys and
the ICVC. Communications
between
the [CVC and the
CCM
is accomplished
through
the SIO (Sensor
Input/
Output) bus, which is a phone cable. The communication
between the CCM and VFD is accomplished
through the
sensor bus, which is a 3-wire cable.
2. If a green LED is on continuously,
check the communica-
tion wiring. If a green LED is off. check the red LED
operation.
If the red LED is normal, check the module
address
switches
(SWI)
(Fig. 44 and 45). Confirm
_dl
switches _ue in OFF position.
All system
operating
intelligence
resides in the ICVC.
Some safety shutdown
logic resides in the Gateway
in
case communications
are lost between
the VFD
and
ICVC. Outputs
are controlled
by the CCM and VFD as
well.
3. Power is supplied to the modules within the control panel
via the 24-vac TI and T2 transformers.
The transformers
_u'e located within the power panel.
In the power panel, TI supplies power to the compressor
oil heatel: and optional hot gas bypass, and T2 supplies
power to both the ICVC and CCM.
T3 provides
24V power to the optiomd DataPort
TM
or
DataLINK
TM
modules.
Power is connected
to Plug Jl on each module.
Chiller Control
Module
(CCM) (Fig
45)
INPUTS
-- Each input channel has 2 or 3 terminals. Refer to
individual
chiller
wiring
diagrams
for the con'ect
terminal
numbers for a specific application.
OUTPUTS-
Output
is 24 vac. There are 2 termimds per
output.
Refer to the chiller
wiring
diagram
for a specific
application
for the correct terminal numbel_.
CONTRAST
ADJUSTMENT
MODULE
PART NUMBER
SOFTWARE
PART NUMBER
@
BACK OFICVC
o
o @
o
\
ICVC
[
/
/
\
J7 SIO
J1 POWER/
J8 SERVICE
CCN
CCN INTERFACE
CONNECTION
/
We
• /
m
DATALINK
OR
DATAPORT
MODULE
(OPTION)
[]
CB1
SWl
Fig 44 -- Rear of ICVC (International Chiller Visual Controller)
97