Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR Installation Instructions Manual
Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR Installation Instructions Manual

Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR Installation Instructions Manual

Hermetic centrifugal liquid chillers with hfc-134a
Hide thumbs Also See for HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR:

Advertisement

Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design speci-
fications. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to equip-
ment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the machine instruc-
tions, as well as those listed in this guide.
DO NOT VENT refrigerant relief devices within a building. Outlet from
rupture disc or relief valve must be vented outdoors in accordance with
the latest edition of ANSI/ASHRAE 15 (American National Standards
Institute/American Society of Heating, Refrigeration and Air-Conditioning
Engineers) (Safety Code for Mechanical Refrigeration). The accumu-
lation of refrigerant in an enclosed space can displace oxygen and cause
asphyxiation.
PROVIDE
adequate
ventilation
ASHRAE 15, especially for enclosed and low overhead spaces. Inha-
lation of high concentrations of vapor is harmful and may cause heart
irregularities, unconsciousness, or death. Intentional misuse can be fa-
tal. Vapor is heavier than air and reduces the amount of oxygen avail-
able for breathing. Product causes eye and skin irritation. Decompo-
sition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine for
any purpose. Oxygen gas reacts violently with oil, grease, and other
common substances.
DO NOT USE air to leak test. Use only refrigerant or dry nitrogen.
NEVER EXCEED specified test pressures. VERIFY the allowable test
pressure by checking the instruction literature and the design pressures
on the equipment nameplate.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and func-
tioning before operating any machine.
RISK OF INJURY OR DEATH by electrocution. High voltage is present
on motor leads even though the motor is not running when a solid state
or inside-delta mechanical starter is used. Open the power supply dis-
connect before touching motor leads or terminals.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller. Traces
of vapor should be displaced with dry air or nitrogen and the work area
should be well ventilated. Refrigerant in contact with an open flame
produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control
panels, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-state
components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before
resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.
USE SAFETY GOGGLES. Wash any spills from the skin with soap
and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 211
Catalog No. 531-940
Tab
5a

Installation Instructions

SAFETY CONSIDERATIONS

in
accordance
with ANSI/
Printed in U.S.A.
Hermetic Centrifugal Liquid Chillers
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat re-
frigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emp-
tied, evacuate remaining gas pressure, loosen the collar, and unscrew
and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the
machine. The introduction of the wrong refrigerant can cause
machine damage or malfunction.
Operation of this equipment with refrigerants other than those cited
herein should comply with ANSI/ASHRAE15 (latest edition). Contact
Carrier for further information on use of this machine with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
machine is under pressure or while machine is running. Be sure pres-
sure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates
in a corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any
relief valve when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace the
valve.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a machine. Use platform, catwalk, or staging. Fol-
low safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move
inspection covers or other heavy components. Even if components are
light, use mechanical equipment when there is a risk of slipping or
losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE
THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead
of the starter, tower fan, and pumps. Shut off the machine or pump
before servicing equipment.
USE only repaired or replacement parts that meet the code require-
ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process con-
trol group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other
items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corro-
sion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
Form 19XR-2SI
50/60 Hz
with HFC-134a
Pg 1
10-97
Replaces: 19XR-1SI
19XR

Advertisement

Table of Contents
loading

Summary of Contents for Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR

  • Page 1: Safety Considerations

    Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE15 (latest edition). Contact Carrier for further information on use of this machine with other refrigerants. DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running.
  • Page 2: Table Of Contents

    The rigging, installation, field wiring, field pip- ing, and insulation of waterbox covers are the responsibility of the contractor and/or customer. Carrier has no installation responsibilities for the equipment. Job Data Necessary information consists of: •...
  • Page 3 Fig. 1 — Model Number Identification...
  • Page 4 FRONT TOP VIEW 1 — Oil Level Sight Glass 2 — Diffuser Actuator (Hidden/19XR5 Only) 3 — Discharge Isolation Valve 4 — Condenser Pumpout Connection 5 — Condenser Safety Relief Valves 6 — Three-Way Condenser Relief Valve 7 — Hot Gas Bypass Line 8 —...
  • Page 5 COMPRESSOR COOLER MAXIMUM FRAME SIZE* SIZE WEIGHT (lb) 10-12 18,500 15-17 19,000 20-22 19,500 30-32 21,000 2 or 3 35-37 22,500 40-42 29,700 45-47 31,800 50-52 32,200 55-57 33,200 50-52 32,530 55-57 34,230 60-62 39,950 65-67 36,950 *The first digit of the 3-digit compressor code indicates the frame size of the compressor. NOTES: 1.
  • Page 6 COMPRESSOR COOLER MAXIMUM FRAME SIZE* SIZE WEIGHT (lb) 70-72 40,410 75-77 44,210 70-72 45,600 75-77 49,400 80-82 54,900 85-87 58,300 *The first digit of the 3-digit compressor code indicates the frame size of the compressor. CG — Center of Gravity NOTES: 1.
  • Page 7 TUBE REMOVAL SPACE FOR EITHER END 10'-0" (3048 mm) MOTOR SERVICE (SIZES 10-12, 20-22) CLEARANCE 12'-3 1/2" (3747 mm) 4'0"- (1219 mm) (SIZES 15-17) 12'-3 1/2" (3747 mm) (SIZES 30-32, 40-42, 50-52, 60-62) 14'-3" (4343 mm) (SIZES 35-37, 45-47, 55-57, 65-67) 14'-0"...
  • Page 8 Table 2 — 19XR Dimensions (Marine Waterbox) HEAT EXCHANGER SIZE 10 to 12 15 to 17 20 to 22 30 to 32 35 to 37 40 to 42 45 to 47 50 to 52 55 to 57 60 to 62 65 to 67 70 to 72 75 to 77...
  • Page 9 MOTOR Total Compressor Weight* CODE 60 Hz 3,755 3,805 3,870 3,950 3,950 4,659 4,685 4,710 4,737 4,751 4,806 4,874 6,112 6,138 6,216 6,224 6,274 6,364 6,412 6,466 8,025 11,085 11,160 11,181 11,271 11,335 11,434 *Compressor weight is comprised of compressor, stator, rotor, end bell, suction elbow, and dis- charge elbow.
  • Page 10 ENGLISH Dry Rigging Weight (lb) CODE Refrigerant Cooler Condenser Weight Only Only Cooler Condenser Cooler Condenser 2,742 2,704 2,812 2,772 2,883 2,857 3,003 2,984 3,089 3,068 3,176 3,173 3,442 3,523 3,590 3,690 3,746 3,854 4,137 3,694 4,319 3,899 4,511 4,100 4,409 4,606 4,617...
  • Page 11 Table 7 — 19XR Additional Data for Marine Waterboxes* HEAT EXCHANGER FRAME, PASS Psig FRAME 2, 1 AND 2 PASS FRAME 2, 2 PASS FRAME 3, 1 AND 2 PASS FRAME 3, 2 PASS FRAME 4, 1 AND 3 PASS FRAME 4, 2 PASS FRAME 5, 1 AND 3 PASS FRAME 5, 2 PASS...
  • Page 12 NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6. RIG MACHINE COMPONENTS — Refer to instructions below, Fig. 6-9, and Carrier Certified Prints for machine com- ponent disassembly. IMPORTANT: Only a qualified service technician should perform this operation.
  • Page 13 NOTE: Wiring must also be disconnected. Label each wire before removal (see Carrier Certified Prints). In order to dis- connect the starter from the machine, remove wiring for the oil pump, oil heater, control wiring at the power panel, and the main motor leads at the starter lugs.
  • Page 14 3. Disconnect the compressor discharge elbow at the com- pressor (Fig. 7, Item 3). 4. Cut the hot gas bypass line at the location shown (Fig. 6, Item 1). 5. Unbolt the cooler liquid feed line at the location shown (Fig.
  • Page 15 1 — Guide Vane Actuator Cable 2 — Power Panel to Starter Cables (Oil Pump Power, Control Power, and Communication) Fig. 7 — 19XR Chiller Top View 1 — Motor Temperature Sensor Cable 2 — Bearing Temperature Sensor Cable Connection (Inside Box) 3 —...
  • Page 16 1 — Guide Vane Actuator 2 — Diffuser Actuator 3 — Water Temperature Sensor Cables Fig. 9 — Chiller End View...
  • Page 17: Install Machine Supports

    INSTALL ACCESSORY ISOLATION (if required) — Un- even floors or other considerations may dictate the use of accessory soleplates (supplied by Carrier for field installa- tion) and leveling pads. Refer to Fig. 10 and 12. Level machine by using jacking screws in isolation sole- plates.
  • Page 18 2. Accessory (Carrier supplied, field installed) soleplate package includes 4 soleplates, 16 jacking screws and leveling pads. NOTE: The accessory spring isolators are supplied by Carrier for installation in the field. Obtain specific details on spring mounting and machine weight distribution from job data. Also, check job data for methods to support and isolate pipes that are attached to spring isolated machines.
  • Page 19: Connect Piping

    Connect Piping INSTALL WATER PIPING TO HEAT EXCHANGERS — Install piping using job data, piping drawings, and proce- dures outlined below. A typical piping installation is shown in Fig. 14. Factory-supplied insulation is not flammable but can be damaged by welding sparks and open flame. Protect in- sulation with a wet canvas cover.
  • Page 20 NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES COOLER WATERBOXES PASS *Refer to certified drawings. Fig. 15 — Piping Flow Data (NIH, Frames 1 Through 6) NOZZLE-IN HEAD WATERBOXES FRAMES 1, 2, AND 3 FRAMES 4, 5, AND 6 PASS Arrangement Code* CONDENSER WATERBOXES...
  • Page 21 NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES COOLER WATERBOXES PASS *Refer to certified drawings. Fig. 16 — Piping Flow Data (NIH, Frames 7 and 8) NOZZLE-IN-HEAD WATERBOXES FRAMES 7 AND 8 PASS Arrangement Code* CONDENSER WATERBOXES Arrangement Code*...
  • Page 22 *There is no Frame 1 marine waterbox. COOLER WATERBOXES PASS Fig. 17 — Piping Flow Data (MWB, Frames 2 and 3) MARINE WATERBOXES FRAMES 2 AND 3* NOZZLE ARRANGEMENT CODES CONDENSER WATERBOXES Arrangement Code — — — — Arrangement Code —...
  • Page 23 MARINE WATERBOXES (cont) FRAMES 4, 5, AND 6 NOZZLE ARRANGEMENT CODES COOLER WATERBOXES PASS Arrangement Code FRAMES 7 AND 8 NOZZLE ARRANGEMENT CODES COOLER WATERBOXES PASS Arrangement Code Fig. 18 — Piping Flow Data (MWB, Frames 4 Through 8) CONDENSER WATERBOXES Arrangement Code —...
  • Page 24 Table 9 — 19XR Waterbox Nozzle Sizes FRAME PRESSURE PASS SIZE psig (kPa) 150/300 (1034/2068) 150/300 (1034/2068) 150/300 (1034/2068) 150/300 (1034/2068) 150/300 (1034/2068) 150/300 (1034/2068) (1034) (2068) (1034) (2068) NOMINAL PIPE SIZE (in.) Cooler Condenser ACTUAL PIPE ID (in.) Cooler Condenser 7.981 7.981...
  • Page 25 TANK SIZE 0428 10- 5 9-10 ⁄ 0452 14-11 ⁄ 14- 4 ⁄ ⁄ ⁄ TANK SIZE 0428 3175 2997 1448 0452 4553 4382 1546 NOTES: Denotes center of gravity. 2. Dimensions in ( ) are in millimeters. 3. The weights and center of gravity values given are for an empty storage tank. 4.
  • Page 26 RATED DRY WEIGHT AND REFRIGERANT CAPACITY TANK TANK OD SIZE (in.) 0428 24.00 0452 27.25 TANK TANK OD SIZE (mm) 0428 0452 LEGEND ASHRAE — American Society of Heating, Refrigeration, and Air Conditioning Engineers — Outside Diameter — Underwriters’ Laboratories *The above dry weight includes the pumpout condensing unit weight of 210 lbs (95 kg).
  • Page 27 Fig. 20 — Optional Pumpout System Piping Schematic with Storage Tank Fig. 21 — Optional Pumpout System Piping Schematic without Storage Tank...
  • Page 28: Relief Valves

    Additional spare sensors and Carrier Comfort Network modules may be specified as well. These are wired to the machine control panel as indi- cated in Fig.
  • Page 29 Fig. 24 — Carrier Comfort Network Communication Bus Wiring LEGEND *Field supplied terminal strip must be located in control panel. Factory Wiring Field Wiring Fig. 25 — COMM1 CCN Communication Wiring For Multiple Chillers (Typical)
  • Page 30: Connect Starter

    Certified field wiring and dimensional dia- grams are available on request. NOTES: 1. All wiring must comply with applicable codes. 2. Refer to Carrier System Design Manual for details regarding pip- ing techniques. 3. Wiring not shown for optional devices such as: • remote start-stop •...
  • Page 31 Certified field wiring and dimensional dia- grams are available on request. NOTES: 1. All wiring must comply with applicable codes. 2. Refer to Carrier System Design Manual for details regarding pip- ing techniques. 3. Wiring not shown for optional devices such as: • remote start-stop •...
  • Page 32 If primary pump and tower fan motor are controlled by other means, also provide a parallel means for control by Carrier. Do not use starter control transformer as the power source for pilot relay loads.
  • Page 33 If primary pump and tower fan motor are controlled by other means, also provide a parallel means for control by Carrier. Do not use starter control trans- former as the power source for pilot relay loads.
  • Page 34: Carrier Comfort Network Interface

    Voltage to terminals LL1 and LL2 comes from a con- trol transformer in a starter built to Carrier specifica- tions. Do not connect an outside source of control power to the compressor motor starter (terminals LL1 and LL2).
  • Page 35: Install Field Insulation

    Install Field Insulation Protect insulation from weld heat damage and weld splatter. Cover with wet canvas cover during water piping installation. When installing insulation at the jobsite, insulate the fol- lowing components: • compressor motor • cooler shell • cooler tube sheets •...
  • Page 38 Copyright 1997 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 211 Catalog No. 531-940 Printed in U.S.A. Form 19XR-2SI Pg 38 10-97 Replaces: 19XR-1SI...
  • Page 39: Installation Start-Up Request Checklist

    8. The motor starter has not been supplied by Carrier. It has been installed according to the manufacturer’s instructions. 9. The motor starter has not been supplied by Carrier and it has been checked for proper operation. COMMENTS: Serial Number:...
  • Page 40 Concerns about the installation/request for additional assistance: I am aware that the start-up time for a Carrier chiller can take between 2 and 6 days depending on the model of the machine and the options and accessories used with it.

Table of Contents