Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 80

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

COOLER
CONDENSER
PRESSURE
TRANSDUCER
AND
OPTIONAL
WATERSIDE
FLOW
DEVICE
CALI-
BRATION
-- Calibration
can be checked
by compming
the
plessme leadings from file transducer
to an accurate refrigera-
tion gage leading.
These readings can be viewed or calibrated
from the HEAT_EX
screen on the ICVC. The transducer
can
be checked grad calibrated
fit 2 pressure points. These calibra-
tion points me 0 psig (0 kPa) and between
25 and 250 psig
(173 and 1724 kPa). To calibrate these transducers:
1. Shut down the compressor,
coolek and condenser
pumps.
NOTE:
There
should
be no flow through
the heat
exchangers.
2. Disconnect
the transducer
in question
from its Schmder
fitting for cooler or condenser
transducer
calibration.
For
oil pressure or flow device calibration
keep transducer
in
place.
NOTE:
If the
cooler
or condenser
vessels
are at
0 psig (0 kPa) or are open to atmospheric
pressure,
the
transducers
can be calibrated
for zero without
remov-
ing the transducer
from the vessel.
3. Access the HEAT_EX
scleen
and view the particular
transducer
reading
(the EVAPORATOR
PRESSURE
or
CONDENSER
PRESSURE
parameter
on the HEAT
EX
screen).
To calibrate
oil pressure
or liquidside
flow
device, view the particular
reading
(CHILLED
WATER
DELTA P and CONDENSER
WATER DELTA P on the
HEAT_EX
screen,
and OIL PUMP
DELTA
P on the
COMPRESS
screen). It should read 0 psi (0 kPa). If the
reading is not 0 psi (0 kPa), but within _+5 psi (35 kPa),
the value may be set to zero by pressing the
softkey
while the appropriate
transducer
ptuameter
is
highlighted
on the ICVC screen. Then press the
softkey.
The value will now go to zero. No high end
calibration
is necessary for OIL PRESSURE
DELTA P or
flow devices.
If the transducer
value
is not within
the calibration
range, the transducer
returns to the original
reading.
If
the pressure is within
the allowed
range (noted above),
check the voltage
ratio of the transducer.
To obtain the
voltage
ratio,
divide
the voltage
(dc) input
from
the
transducer
by the TRANSDUCER
VOLTAGE
REF
supply
voltage
signal
(displayed
in CONTROL
TEST
menu in the PRESSURE
TRANSDUCERS
screen) or
measure
across
the
positive
(+ red)
and
negative
(- black)
leads
of the transducer.
For example,
the
condenser
transducer
voltage
reference
is measured
fit CCM terminals
J2-4 and J2-6, the condenser
trans-
ducer
voltage
input.
The input
to reference
voltage
ratio must be between
0.80 and 0.11 for the software
to
allow calibration.
Pressurize
the transducer
until the
ratio is within range. Then attempt
calibration
again.
4. A high pressure point can fdso be calibrated
between 25
and 250 psig (172.4 and 1723.7 kPa) by attaching a regu-
lated
250 psig
(1724 kPa)
pressure
(usually
from
a
nitrogen
cylinder).
The
high
pressure
point
can
be
calibrated
by accessing the appropriate
transducer
pmam-
eter on the HEAT_EX
screen, highlighting
the pm'ametek
pressing
the _
softkey,
and
then using
the
[INCREASE 1 or [DECREASE]
softkeys
to adjust
the
vfdue to the exact pressure on the refrigerant gage. Press
the _
softkey to finish the calibration.
Pressures fit
high altitude
locations must be compensated
fok so the
chiller temperature/pressure
relationship
is correct.
The PIC III does not allow calibration
if the transducer
is
too far out of calibration.
In this case, a new transducer
must be
installed and re-calibrated.
If calibration
problems are encoun-
tered on the OIL PRESSURE
DELTA P channel,
sometimes
swapping the compressor
oil discharge pressure transducer
and
the oil sump pressure transducer
will offset an adverse trans-
ducer tolerance
stack up and allow the calibration
to proceed.
TRANSDUCER
REPLACEMENT
-- Since the transducers
are mounted
on Schrader-type
fittings,
there is no need to
remove refrigerant
from the vessel when replacing
the trans-
ducers. Disconnect
the transducer
winng.
Do not pull on the
transducer
wires. Unscrew
the transducer from the Schmder
fitting. When instfdling a new transducer, do not use pipe sealer
(which can plug the sensor). Put the plug connector
back on the
sensor and snap into place. Check for refi'igerant leaks.
Be sure to use a back-up wrench
on the Schrader
fitting
whenever
removing a transducek
since the Schmder
fitting
may back out with the transducek
causing an uncontrolled
loss of refrigerant and possible injury to personnel.
Control Algorithms
Checkout
Procedure
-- One
of the tables on the [CVC
SERVICE
menu is CONTROL
ALGORITHM
STATUS.
The maintenance
screens
may be
viewed from the CONTROL
ALGORITHM
STATUS table to
see how a particulm control algorithm is operating.
These maintenance
screens
are very useful in helping to
determine
how the control temperature
is calculated
and guide
vane positioned
and also for observing
the leactions
from load
changes, control point overrides, hot gas bypass, surge preven-
tion, etc. The tables are:
Table 15-
Control
Algorithm
Status
Tables
TABLE
EXPANDED
DESCRIPTION
NAME
CAPACITY
Capacity
This tableshows all values used to
Control
calculate the chilled water/brine
control point.
OVERRIDE
Override
Details of all chilled water control
Status
override values.
LL MAINT
LEAD/LAG
Indicates LEAD/LAG operation
Status
status.
OCCDEFCM
Time
The Local and CCN occupied
Schedules
schedules are displayed here to
Status
help the operator quickly deter-
mine whether the schedule is in
the "occupied" mode or not.
WSMDEFME
Water
The water system manager is a
System
CCN module that can turn on the
Manager
chiller and change the chilled water
Status
control point, This screen indicates
the status of this system.
VFD HIST
VFD Alarm
Displays VFD values at last fault.
History
LOADSHED
Loadshed
DisplaysLeadshed (Demand Limit)
Status
status.
CURALARM
Current
Displays current chiller alarms.
Alarm Status
Surge and hot gas bypass parameters
may be observed
in
the HEAT_EX
screen. The surge and hot gas bypass control
algorithm
status is viewed from tiffs screen. All values defiling
wifll this control are displayed.
8O

Advertisement

Table of Contents
loading

Table of Contents