Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 82

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Table
16 -- Alarm and Alert Messages
(cont)
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.
ICVC FAULT
PRIMARY
SECONDARY
STATE
MESSAGE
MESSAGE
PRIMARY CAUSE
ADDITIONAL
CAUSE/REMEDY
100
PRESTART
STARTS LIMIT
100_Excessive
compressor
starts
Depress the RESET softkey if additional start
ALERT
EXCEEDED
(8 in 12 hours),
is required. Reassess start-up requirements.
101
PRESTART
HIGH BEARING
101_Comp
Thrust Brg Temp [VALUE]
Check oil heater for proper operation.
ALERT
TEMPERATURE
exceeded limit of [LIMIT]*.
Check for low oil level, partially closed oil sup-
ply valves, clogged oil filters.
Check the sensor wiring and accuracy.
Check Comp Thrust Brg Alert setting in
SETUP1 screen.
102
PRESTART
HIGH MOTOR
102-_Comp
Motor Winding Temp
Check motor sensors for wiring and accuracy.
ALERT
TEMPERATURE
[VALUE] exceeded limit of [LIMIT]*.
Check motor cooling line for proper operation,
or restrictions.
Check for excessive starts within a short time
span.
Check Comp Motor Temperature
Override
setting in SETUP1 screen.
103
PRESTART
HIGH
103_Comp
Discharge Temp [VALUE]
Allow discharge sensor to cool.
ALERT
DISCHARGE
exceeded limit of [LIMIT]*.
Check sensor wiring and accuracy.
TEMP
Check for excessive starts.
Check Comp Discharge Alert setting in
SETUP1 screen.
104
PRESTART
LOW
104-_Evaporator
Refrig Temp [VALUE]
Check transducer wiring and accuracy.
ALERT
REFRIGERANT
exceeded limit of [LIMIT]*.
Check for low chilled fluid supply
TEMP
temperatures.
Check refrigerant charge.
Check Refrig Override Delta T in SETUP1
screen.
105
PRESTART
LOW OIL
105_Oil
Sump Temp [VALUE]
Check oil heater contactor/relay
and power.
ALERT
TEMPERATURE
exceeded limit of [LIMIT]*.
Check oil level and oil pump operation.
106
PRESTART
HIGH
106_Condenser
Pressure [VALUE]
Check transducer wiring and accuracy.
ALERT
CONDENSER
exceeded limit of [LIMIT]*.
Check for high condenser water
PRESSURE
temperatures.
Check high condenser pressure switch wiring.
107
PRESTART
LOW LINE
107-_Percent
Line Voltage [VALUE]
Check voltage supply.
ALERT
VOLTAGE
exceeded limit of [LIMIT]*.
Check voltage transformers
and switch gear.
Consult power utility if voltage is low.
108
PRESTART
HIGH LINE
108_Percent
Line Voltage [VALUE]
Check voltage supply.
ALERT
VOLTAGE
exceeded limit of [LIMIT]*.
Check power transformers.
Consult power utility if voltage is high.
109
PRESTART
GUIDE VANE
109_Actual
Guide Vane Pos
Press STOP button on ICVC and perform
ALERT
CALIBRATION
Calibration Required Before Startup.
Guide Vane Calibration in Controls Test
screen.
Check guide vane actuator feedback
potentiometer.
110
PRESTART
HIGH
110_Rectifier
Temperature
[VALUE]
Check that VFD refrigerant isolation valves
ALERT
RECTIFIER
exceeded limit of [LIMIT]*.
are open.
TEMP
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
111
PRESTART
HIGH
111-_lnverter
Temperature [VALUE]
Check that VFD refrigerant isolation valves
ALERT
INVERTER
exceeded limit of [LIMIT]*.
are open.
TEMP
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual pressure, temperature, voltage, etc., at which the control tripped.
E. START-UP
IN PROGRESS
PRIMARY MESSAGE
SECONDARY
MESSAGE
CAUSE/REMEDY
STARTUP IN PROGRESS
OCCUPIED
MODE
Chiller is starting. Time schedule is Occupied.
STARTUP IN PROGRESS
REMOTE CONTACT CLOSED
Chiller is starting. Remote contacts are Enabled and Closed.
STARTUP IN PROGRESS
START COMMAND
IN EFFECT
Chiller is starting. Chiller START/STOP in MAINSTAT manually forced to
start.
AUTORESTART
IN
OCCUPIED
MODE
Chiller is starting after power failure. Time schedule is Occupied.
PROGRESS
AUTORESTART
IN
REMOTE CONTACT CLOSED
Chiller is starting after power failure. Remote contacts are Enabled and
PROGRESS
Closed.
AUTORESTART
IN
START COMMAND
IN EFFECT
Chiller is starting after power failure. Chiller START/STOP on MAINSTAT
PROGRESS
screen manually forced to start.
82