Leak Test Chiller; Standing Vacuum Test - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Leak Test
Chiller
--
Due to regulations
regarding refiig-
erant emissions
and the difficulties
associated
with separating
contaminants
from the refrigerant,
Carrier recommends
the
following
leak test procedure.
See Fig. 29 for an outline of the
leak test procedure.
Refer to Fig. 30 and 31 during pumpout
procedures
and Tables
11A and 11B for refi'igerant
pressure/
temperature
values.
1. [f the
pressure
readings
are
normal
for
the chiller
condition:
a.
Evacuate
the holding
charge
fiom the vessels,
if
present.
b.
Raise the chiller
pressure,
if necessary,
by adding
refrigerant
until pressure
is at the equivalent
satu-
rated
pressure
for the surrounding
temperature.
Follow
the pumpout
procedures
in the Transfer
Refrigerant
from Pumpout
Storage
Tank to Chiller
section, Steps I a - e, page 72.
Never charge liquid refrigerant
into the chiller if the pres-
sure in the chiller
is less than 35 psig (241 kPa) for
HFC-134a.
Charge
as a gas only, with the cooler
and
condenser
pumps running,
until this pressure
is reached,
using
PUMPDOWN
LOCKOUT
and
TERMINATE
LOCKOUT
mode
on the PIC
III. Flashing
of liquid
lefrigerant
at low pressures
can cause tube freeze-up
and
considerable
damage.
c.
Leak test chiller as outlined
in Steps 3-9.
2. If the pressure
readings
are abnormal
for the chiller
condition:
a.
Prepare
to leak test chillers
shipped
with refriger-
ant (Step 2h).
b.
Check for large leaks by connecting
a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap
test all joints. If the test pressure holds for 30 minutes,
prepare the test for small leaks (Steps 2g-h).
c.
Plainly mark any leaks that are found.
d.
Release the pressure
in the system.
e.
Repair all leaks.
f.
Retest the joints that were repaired.
g.
After
successfully
completing
the test for large
leaks, remove
as much nitrogen,
air. and moisture
as possible,
given the fact that small leaks may be
present in the system. This can be accomplished
by
following
the dehydration
procedure,
outlined
in
the Chiller
Dehydration
section, page 58.
h.
Slowly raise the system pressure
to a maximum
of
160 psig
(1103
kPa)
but no less than
35 psig
(241 kPa)
for HFC-134a
by adding
refrigerant.
Proceed
with the test for small leaks (Steps 3-9).
3. Check the chiller carefully with an electronic
leak detec-
tol: halide torch, or soap bubble solution.
4. Leak Determination
--If
an electronic
leak detector
indicates a leak, use a soap bubble solution, if possible, to
confirm. Total all leak rates for the entire chillel: Leakage
at rates greater than 0.1% of the total charge per year must
be repaired. Note the toted chiller leak rate on the start-up
_eport.
5. If no leak is found during the initi_d start-up procedures,
complete the transfer of refrigerant
gas from the pumpout
storage tank to the chiller (see Transfer Refiigerant
from
Pumpout
Storage
Tank
to Chiller
section,
page
72).
Retest for leaks.
6. If no leak is found after a retest:
a.
Transfer
the refrigerant
to the pumpout
storage
tank
and
perform
a
standing
vacuum
test
as
outlined
in the Standing
Vacuum
Test
section,
below.
b.
If the chiller fails the standing
vacuum
test, check
for large leaks (Step 2b).
c.
If the chiller
passes
the standing
vacuum
test,
dehydrate
the
chiller.
Follow
the procedure
in
the Chiller Dehydration
section.
Charge the chiller
with
refrigerant
(see Transfer
Refrigerant
fiom
Pumpout
Storage
Tank
to
Chiller
section,
page 72).
7. If a leak is found after a retest, pump the refrigerant
back
into the pumpout
storage tank or, if isolation
valves are
present,
pump
the
refrigerant
into
the
non-leaking
vessel (see Pumpout and Refrigerant
Transfer procedures
section).
8. Transfer
the refrigerant
until the chiller
pressure
is at
18 in. Hg (40 kPa absolute).
9. Repair the leak and repeat the procedure, beginning
from
Step 2h, to ensure a leak-tight
repail: (If the chiller
is
opened to the atmosphere
for an extended period, evacu-
ate it before repeating the leak test.)
Standing Vacuum Test
--
When perforlning
the stand-
ing vacuum
test or chiller dehydi'ation,
use a manometer
or a
wet bulb indicatol: Dial gages cannot indicate the small amount
of acceptable
leakage during a short period of time.
1. Attach
an absolute
pressure
manometer
or wet
bulb
indicator to the chillel:
2. Evacuate
the
vessel
(see
Pumpout
and
Refrigerant
Transfer Procedures
section, page 71 ) to at least 18 in. Hg
vac, ref 30-in. bar (41 kPa), using a vacuum pump or the
pump out unit.
3. Valve off the pump to hold the vacuum
and record the
manometer
or indicator reading.
4. a. If the leakage rate is less than 0.05 in. Hg (0.17 kPa) in
24 hours, the chiller is sufficiently
tight.
b.
ffthe leakage rate exceeds 0.05 in. Hg (0.17 kPa) in
24 hours, repressurize
the vessel and test for leaks.
If refrigerant
is available
in the other vessel, pressur-
ize by following
Steps 2-10 of Return
Chiller
To
Normal
Operating
Conditions
section,
page 73. If
not, use nitrogen
and a refi'igerant
tracer
Raise the
vessel
plessure
in increments
until
the
leak
is
detected.
If refrigerant
is used, the maximum
gas
pressure
is approximately
70 psig
(483 kPa) for
HFC-134a
at normal ambient
temperature.
If nitro-
gen is used, limit the leak test pressure
to 160 psig
(1103 kPa) maximum.
55

Advertisement

Table of Contents
loading

Table of Contents