Head Pressure Reference Output; Lead/Lag Control; Lead/Lag Operation; Wiring - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Head Pressure Reference
Output (See Fig. 24) --
The PIC [II control
outputs
a 4 to 20 mA signal for the
configurable
Delta
P
(CONDENSER
PRESSURE
minus
EVAPORATOR
PRESSURE)
leference cmwe shown in Fig. 24.
The DELTA P AT 100% (chiller at maximum
load condition
default at 50 psi), DELTA P AT 0% (chiller at minimum
load
condition
default at 25 psi) trod MINIMUM
OUTPUT
points
are configurable
in the EQUIPMENT
SERVICE-OPTIONS
ta-
ble. When configuring
this output ensure that minimum
re-
quirements
for oil pressure and proper condenser
FLASC on-
lice performance
are mtdntained.
The 4 to 20 mA output from
VFD TBI terminals
17 and 18 may be useful as a reference
signal to control a towel bypass
valve, tower speed control,
condenser
pump speed control, etc. Note that it is up to the site
design engineering
agent to integrate
this analog output with
any external
system device(s)
to produce
the desired
effect.
Carrier does not make any claim that this output is directly us-
able to control any specific piece of equipment
(that is, without
further control elements
or signal conditioning),
although
it
may be.
The head pressure reference output will be on whenever
the
condenser
pump is operating.
It may also be manually operated
in CONTROLS
TEST. When the head pressure differential
is
less than the value entered forDELTA
PATO%,
the output will
be maintained
at 4 mA.
Lead/Lag Control
--
The lead/lag control system auto-
matically starts and stops a lag or second chiller in a 2-chiller
water system.
A third chiller
can be added to the lead/lag
system as a standby chiller to start up in case the lead or lag
chiller in the system has shut down during an ahum condition
and additional
cooling is required. Refer to Fig. 17 and 18 for
menu, table, and screen selection information.
NOTE: The lead/lag function can be configured
on the LEAD-
LAG screen, which is accessed
from the SERVICE
menu and
EQUIPMENT
SERVICE
table.
See Table 4, Example
20.
Lead/lag
status during chiller operation
can be viewed on the
LL_MAINT
display
screen,
which
is accessed
from
the
SERVICE
menu
and CONTROL
ALGORITHM
STATUS
table. See Table 4, Example
12.
Lead/Lag System Requirements:
all chillers
in the system
must have software
capable
of
performing
the lead/lag
function
water
pumps
MUST
be energized
from
the
PIC
III
controls
water flows should be constant
the CCN time schedules
for all chillers
must be identical
Operation Features:
• 2chiller lead/lag
DELTAP
AT100% "3
DE LTA P
DELTA P__
AT0%
l NON-ZERO
',EXAMPLE OF
' M N MUM
',REFERENCE
',OUTPUT
s" a"
i
t
===7
= ..........
0mA 2 mA4mA
(O%)
4T0 20 mA OUTPUT
Fig. 24-
Head
Pressure
Reference
Output
]11
20 mA
(100%)
addition
of a third chiller for backup
manual
rotation of lead chiller
load balancing
if configured
staggered
restart of the chillers
after a power failure
chillers may be piped in parallel or in series chilled water
flow
COMMON
POINT
SENSOR
USAGE
AND
INSTALLA-
TION-
Lead/lag
operation
does
not require
a common
chilled water point sensor
However.
common
point sensors
(Spare Temp #1 and #2) may be added to the CCM module, if
desired.
NOTE:
If the common
point sensor
option
is chosen
on a
chilled water system, each chiller should have its own common
point sensor installed. Each chiller uses its own common
point
sensor for control when that chiller is designated
as the lead
chillel: The PIC III cannot read the value of common
point
sensors
installed
on the other
chillers
in the chilled
water
system.
If leaving chilled water control (ECW CONTROL
OPTION
is set to 0 [DSABLEI
TEMP
CTL
screen) and a common
point
sensor
is desired
(COMMON
SENSOR
OPTION
in
LEADLAG
screen selected as 1) then the sensor is wired in
Spare Temp #1 position
on the CCM (terminals
J4-25 and
J4-J26).
If the entering
chilled water control option
(ECW CON-
TROL
OPTION)
is enabled
(configured
in TEMP_CTL
screen)
and a common
point sensor
is desired
(COMMON
SENSOR
OPTION
in LEADLAG
screen selected as 1) then
the sensor is wired in Spare Temp #2 position on the CCM
(terminals J4-27 and J4-28).
When installing
chillers in series, either a common
point
sensor should be used (preferred),
or the LEAVING
CHILLED
WATER sensor of the upstremn chiller must be moved into the
leaving
chilled water pipe of the downstream
chillel: In this
application
the COMMON
SENSOR
OPTION should only be
enabled for the upstremn chiller if that chiller is configured
as
the Lead.
If ENTERING
CHILLED
WATER control
is required
on
chillers piped in series, either the common point return chilled
water sensor
should
be used (preferred),
or the LEAVING
CHILLED
WATER sensor of the downstream
chiller must be
relocated
to the LEAVING
CHILLED
WATER pipe of the
upstream
chiller. In this application
the COMMON
SENSOR
OPTION
should only be enabled for the downstream
chiller if
that chiller is configured
as the Lead. Note that ENTERING
CHILLED
WATER control
is not recommended
for chillers
installed in series due to potential control stability problems.
To properly
control
the LEAVING
CHILLED
WATER
TEMPERATURE
when chillers me piped in parallel, the water
flow through the shutdown
chiller(s) should be isolated so that
no water bypass around the operating chiller occurs. However.
if water bypass around the operating
chiller is unavoi&_ble,
a
common
point
sensor
in the mixed
LEAVING
CHILLED
WATER piping should be provided
and enabled for the Lead
chillel:
CHILLER
COMMUNICATION
WIRING
-- Refer
to the
chiller's
Installation
Instructions,
Cmrier
Comfort
Network
Interface
section
for infommtion
on chiller
communication
wiring.
LEAD/LAG
OPERATION-
The PIC III not only has the
ability to operate
2 chillers in lead/lag,
but it can also start a
designated
standby chiller when either the lead or lag chiller is
faulted and capacity
requirements
are not met. The lead/lag
option only operates when the chillel_ are in CCN mode. If any
other chiller configured
for lead/lag
is set to the LOCAL
or
OFF modes, it will be unavailable
for lead/lag operation.
44

Advertisement

Table of Contents
loading

Table of Contents