Oil Filter - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Inspect the Control Panel
--
Maintenance
consists
of
general
cleaning
and tightening
of connections.
Vacuum
the
cabinet
to eliminate
dust
build-up.
If the chiller
control
malfunctions,
refer to the Troubleshooting
Guide section for
control checks and adjustments.
Ensure power to the control center is off when cleaning and
tightening
connections
inside the control p_mel. Failure to
disconnect
power could result in electrocution.
Check
Safety
and
Operating
Controls
Monthly
--
Check
values
of monitored
parameters
(see
Table 6 for safety control settings).
To ensure chiller protec-
tion, the Automated
Control
Test should
be performed
at
least once per month
(with machine
in OFF mode).
See
Table 12 for Control
Test functions.
Changing
Oil Filter--Change
the
oil
filter
on a
yearly basis or when
the chiller
is opened
for repairs.
The
19XRV chiller
has an isolatable
oil filter so that the filter
may
be changed
with
the refrigerant
remaining
in the
chiller.
Early
19XRV compressors
were designed
with the
oil filter
housing
attached
to the oil pump. The following
procedure
applies
to later 19XRV compressors
which
have
the oil filter separate
flom the oil pump.
1. Ensure the compressor
is off and the disconnect
for the
compressor
is open.
2. Disconnect
the power to the oil pump.
3. Close the oil filter isolation
valves located behind power
panel on top of oil pump assembly.
4. Close the isolation valves located on both ends of the oil
filtel: Have rags and a catch basin available
to collect oil
spillage.
5. Equfdize the filter's
higher internal
pressure to ambient
by connecting
an oil charging hose to the Schmder
valve
on the oil filter housing. Collect the oil-refrigerant
mix-
ture which is dischm'gedi
6. Remove the oil filter assembly by loosening the hex nuts
on both ends of the filter assembly.
7. Insert the replacement
tilter assembly
with the rerow on
the housing pointing away from the oil pump.
8. Rotate the assembly
so that the schraeder
drain vfflve is
oriented fit the bottom, and tighten the connection
nut on
each end to a torque of approximately
30 ft-lb (41 N-m)
The oil filter housing
is at a high pressure.
Relieve
this
pressure slowly. Failure to do so could result in serious per-
sonal injury.
9. Evacuate the filter housing by placing a vacuum pump on
the charging valve. Follow the normal evacuation
proce-
dures. Shut the charging
valve when done and reconnect
the valve so that new oil can be pumped into the filter
housing.
Fill with the stone amount
that was removed;
then close file charging valve.
10. Remove the hose from the chmging valve, open the isola-
tion valves to the filter housing, and turn on the power to
the pump and the motol:
Oil Specification
--
If oil is added, it must meet the fol-
lowing Carrier specifications:
Oil Type for units using R-134a
..................
Inhibited
polyolester-based
synthetic
compressor
oil formatted
for
use with HFC, gear-driven,
hermetic compressors.
ISO Viscosity Grade .................................
68
The
polyolester-based
oil
(P/N:
PP23BZI03)
may
be
ordered from a local Carrier representative.
Oil Changes--Cmrier
recommends
changing
the oil
after the first year of operation
and every three to five years
thereafter
as a minimum
in addition
to a yedy
oil amdysis.
Howevel:
if a continuous
oil monitoring
system is functioning
and a yearly oil analysis
is performed,
file time between
oil
changes can be extended.
TO CHANGE
THE OIL
1. Transfer the refrigerant
into the chiller condenser
vessel
(for isolatable vessels) or to a pumpout storage tank.
2. Mark the existing oil level.
3. Open file control and oil heater circuit breakel:
4. When the chiller pressure is 5 psig (34 kPa) or less, drain
the oil reservoir
by opening
the oil charging
vfdve
(Fig.
2). Slowly
open
the valve
against
refrigerant
pressure.
5. Change the oil filter fit this time. See Changing
Oil Filter
section.
6. Change
the refrigerant
filter fit this time, see the next
section, Refrigerant
Filtec
7. Charge the chiller with oil. Chmge until the oil level is
equal to the oil level marked in Step 2. Turn on the power
to the oil heater and let file PIC [II warm it up to fit least
140 F (60 C). Operate the oil pump manually, using the
Control Test function, for 2 minutes. For shutdown condi-
tions, the oil level should be full in the lower sight glass.
If the oil level is above
1/2
full in the upper sight glass,
remove the excess oil. The oil level should now be equal
to the amount shown in Step 2.
Refrigerant Filter
--
A refrigerant filter/driel,
located on
the refrigerant
cooling
line to the motol; should be changed
once a ye;u or more often if filter condition indicates a need for
more frequent replacement.
Change
the filter by closing the
filter isolation
valves
(Fig. 4) and slowly opening
the flare
fittings with a wrench and back-up wrench to relieve the pres-
sure. A moisture
indicator
sight glass is located beyond
this
filter to indicate the volume and moisture
in the refrigerant.
If
the moisture
indicator
indicates moisture,
locate the source of
water immediately
by performing
a thorough leak check.
Oil Reclaim Filter--The
oil
reclaim
system
has
a
strainer on file eductor suction line, a strainer on the discharge
pressure
line, and
a filter
on the cooler
scavenging
line.
Replace file filter once per year or more often if tilter condition
indicates
a need for more frequent replacement.
Change
the
filter by closing the filter isolation
valves and slowly opening
the flare fitting with a wrench
and back-up wrench to relieve
the pressure. Change the stminel_ once every 5 yeal_ or when-
ever refrigerant
is evacuated
from the coolel:
76

Advertisement

Table of Contents
loading

Table of Contents