Remote Start/Stop Controls; Spare Safety And Spare Temperature Inputs; Alarm (Trip) Output Contacts - Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

Table 7 -- Capacity
Overrides
Table
FIRST STAGE SET POINT
SECOND
STAGE SET POINT
OVERRIDE TERMINATION
OVERRIDE
CONDITION
View/Modify
on
Override
Default
Configurable
Value
Value
ICVC Screen
Value
Range
CONDENSER
CONDENSER
PRESSURE
CONDENSER
PRESSURE
High Condenser
Pressure
SETUP1
PRESSURE
90 to 165 psig
> COND PRESS OVERRIDE
< CONDENSER
PRESS
(COND PRESS OVERRIDE)
>125 psig (862 kPa)
(621 to 1138 kPa)
+ 2.4 psig (16.5 kPA)
OVERRIDE - 1 PSI (6.9 kPa)
High Motor Temperature
COMP MOTOR
150 to 200 F
COMP MOTOR WINDING
TEMP
COMPR MOTOR WINDING
(COMP MOTOR TEMP
SETUP1
WINDING
TEMP
> COMP MOTOR TEMP OVER-
TEMP < COMP MOTOR TEMP
OVERRIDE)
> 2OO F (93 C)
(66 to 93 C)
RIDE + 10 F (5.6 C)
OVERRIDE-
2 F (1.1 C)
EVAPORATOR
REFRIG TEMP
EVAPORATOR
< EVAP REF OVERRIDE TEMP
Low Evaporator
Temperature
REFRIG TEMP
2 to 5 F
- 1 F (.6 C)
EVAP REFRIG TEMP
(REFRIG
OVERRIDE
SETUP1
< EVAP REFRIG
(1.1 to 2.8 C)
NOTE: EVAP REF OVERRIDE
> EVAP REF OVERRIDE TEMP
DELTA T)
TRIPPOINT
+ 3 F
TEMP = EVAP REFRIG TRIP-
+2F(1.1C)
(1.7 C)
POINT + REFRIG OVERRIDE
DELTA T
Min TI: 1.5 F (0.8 C)
0.5 - 2.0 F
(0.3-
1.1 C)
Min PI: 50 psid
30 - 170 psid
ACTIVE DELTA T > SURGE/
High Compressor
Lift
OPTIONS
(345 kPa)
(207 - 1172 kPad)
None
HGBP DELTA T + SURGE/HGBP
(SURGE/HGBP
DELTA T,P)
Max T2:10
F (5.6 C)
0.5 - 20 F
DEADBAND
(0.3- 11,1 C)
Max P2:85
psid
50 - 170 psid
(586 kPad)
(345 - 1172 kPad)
Manual Guide Vane Target
Press RELEASE softkey after
(TARGET GUIDE VANE POS)
COMPRESS
Automatic
0 to 100%
None
selecting TARGET GUIDE VANE
POS
Forced TARGET VFD SPEED
Manual Speed Control
VFD MINIMUM
cannot override either a
Press RELEASE softkey after
capacity inhibit or a capacity
selecting TARGET VFD SPEED
(TARGET VFD SPEED)
COMPRESS
Automatic
SPEED to 100%
decrease command generated by
the PIC III
Motor Load
MAINSTAT
Automatic
40 to 100%
ACTIVE DEMAND LIMIT
ACTIVE DEMAND LIMIT
(ACTIVE
DEMAND
LIMIT)
> Set Point + 5%
< Set Point - 2%
ACTUAL SUPER-
ACTUAL SUPERHEAT
ACTUAL SUPERHEAT
HEAT< SUPERHEAT
None
< SUPERHEAT
REQUIRED
> SUPERHEAT
REQUIRED
Low Discharge
Superheat
OVERRIDE
REQUIRED
for
conditions
- 1.25 F (0,7 C)
+ 1 F (0.56 C)
High Rectifier
Temperature
RECTIFIER
155 to 170 F
RECTIFIER
TEMP
RECTIFIER
TEMP
(RECTIFIER
TEMP
SETUP1
TEMPERATURE>
(66 to 77 C)
> RECTIFIER
TEMP OVERRIDE
< RECTIFIER
TEMP OVERRIDE
OVERRIDE)
160 F (71 C)
+ 10 F (5,6 C)
- 5 F (2.8 C)
High Inverter
Temperature
INVERTER
155 to 170 F
INVERTER TEMP
INVERTER TEMP
(INVERTER
TEMP
SETUP1
TEMPERATURE
>
> INVERTER
TEMP OVERRIDE
< INVERTER
TEMP OVERRIDE
OVERRIDE)
160 F(71 C)
(66 to 77 C)
+ 10 F(5,6C)
-5
F(2.8C)
Remote Start/Stop
Controls -- A
remote device, such
as a timeclock that uses a set of contacts,
may be used to stmt
and stop the chillel: Howevel;
the device should not be pro-
gmmmed
to st_ut and stop file chiller in excess of 2 or 3 times
every 12 hours. If more than 8 st_uts in 12 hom_ (the STARTS
IN 12 HOURS
parmneter
on the MAINSTAT
screen) occur.
(not counting either lecycle restmts or auto restarts after power
failure)
an excessive
starts alarm
displays,
preventing
the
chiller
from starting. Tile operator
must press the
softkey on the ICVC to override the starts counter and start the
chillel: If the chiller records
12 starts (excluding
recycle starts)
in a sliding 12-hour period, it can be lestarted
only by pressing
the _
softkey
followed by the _
or _
soft-
key. This ensures that, if the automatic
system is m_dfunction-
ing, the chiller will not repeatedly
cycle on and off. If the
AUTORESTART
OPTION
in the OPTIONS
scieen
and the
REMOTE
CONTACTS
OPTION
are enabled,
the REMOTE
CONTRACTS
must be closed in order for the chiller to lest_ut
following a power failure. If the automatic
restmt after a power
failure option (AUTO RESTART
OPTION
on file OPTIONS
screen) is not activated when a power failure occurs, and if the
remote
contact
is closed,
the chiller
will indicate
an _darm
because of the loss of voltage.
The contacts for remote start are wired into terminals 23 trod
24 of the low voltage terminal strip in the VFD enclosure.
See
the certified drawings
for further details on contact ratings. The
contacts must have 24 vac dry contact rating.
Spare
Safety
and Spare Temperature
Inputs --
Norln_dly
closed
(NC) discrete
inputs
for addition_d
field-
supplied
safeties may be wired to the spare protective
limits
input
channel
in place
of the factory-installed
jumper
on
terminals
19 and 20 of the low voltage
terminal
strip. The
opening of tiny contact will result in a safety shutdown
and a
display on the ICVC. Refer to the certified drawings
for safety
contact ratings.
Extra amdog telnperature
sensors may also be added to the
CCM
module
(SPARE
TEMPERATURE
#l
and
SPARE
TEMPERATURE
#2) at terminals
J4 25-26 and J4 27-28,
respectively.
The analog temperature
sensors may be config-
ured in the EQUIPMENT
SERVICE/SETUPI
table to cause
an alert (Enable value l or 2) or almm (Enable value 3 or 4),
or neither (Enable value 0). An alarm will shut down a running
chiller,
but an alert
will not. The fault condition
will
be
triggered when crossing a high limit (Enable value 2 or 4) or
low limit (Enable value l or 3), configurable
between -40 F to
245 F (-40 C to 118 C). The spare temperature
sensors are
readable
on the CCN netwoN.
They also have specific uses
as common
temperature
sensors
in a Lead/Lag
system
(see
page 44).
Alarm (Trip) Output
Contacts
-- One set of alarm
contacts
is provided
in file stmlel: The contact
ratings are
provided
in the certified drawings.
The contacts are located on
terminals 9 and l0 of the TB2 field wiring terminal strip in the
VFD enclosure.