Installing The Dc-Input Pem - Cisco 6509 - Catalyst Chassis Switch Installation Manual

Installation guide
Table of Contents

Advertisement

Removing and Installing the Power Entry Modules (PEMs)

Installing the DC-Input PEM

Before performing any of the following procedures, ensure that power is removed from the
Warning
DC circuit. Statement 1003
Warning
When installing or replacing the unit, the ground connection must always be made first and
disconnected last. Statement 1046
Follow these steps to install a DC-input PEM:
Ensure that the system (earth) ground connection has been made. For ground connection installation
Step 1
instructions, see the
Verify that power is off to the DC circuit for the PEM that you are installing. As an added precaution,
Step 2
place the appropriate safety flag and lockout devices at the source power circuit breaker, or place a piece
of adhesive tape over the circuit breaker handle to prevent accidental power restoration while you are
working on the circuit.
Install the PEM part way in the chassis so that you still have access to the PEM terminal block screws.
Step 3
(See
Connect the DC-input wires to the terminal block in this order:
Step 4
1.
2.
After ensuring that all wire connections are secure, install the PEM in the bay.
Step 5
Tighten the power supply captive installation screws. (See
Step 6
In a system with dual power supplies, connect each power supply to a separate input line. In case of
Caution
a line failure, the second source will most likely still be available.
Remove the safety flag, lockout devices, or tape from the circuit breaker switch handle, and restore
Step 7
power by moving the circuit breaker switch handle to the On (|) position.
Verify the power supply operation by ensuring that the power supply front panel LEDs are in the
Step 8
following states:
If the LEDs indicate a power problem, see the
Catalyst 6500 Series Switches Installation Guide
4-56
"Establishing the System Ground" section on page
Figure
4-47.)
Negative (–)
Positive (+)
INPUT OK LED is green
FAN OK LED is green
OUTPUT FAIL LED is not lit
Chapter 4
Removal and Replacement Procedures
3-22.
Figure
4-48.)
"Identifying Startup Problems" section on page
E-3.
OL-5781-04