Installing the Cisco MDS 9513 Director in a Rack

The 6000-W AC power supplies for the Cisco MDS 9513 Director are designed to provide an output
power for the modules and fans. Each power supply has two AC power connections and will provide
power as follows:
Power output does not include the power used by the individual modules used in the chassis.
Note
Installation of the Cisco MDS 9513 Director in a rack requires a mechanical lift to place the chassis in
the rack. Ensure that you have access to the lift during the installation process.
Table 2-1
The rack-mount kit for the Cisco MDS 9513 Director includes rack-mount support brackets, which are
Note
required for the duration of the installation and are not removable.
Table 2-1
Quantity
2
2
20
20
To install the Cisco MDS 9513 chassis in a rack using the rack-mount kit provided with the switch,
follow these steps:
Adjust the distance between the front and rear cabinet vertical rack-mount rails to 26.56 ± 0.15 in. (67.46
Step 1
cm). This step must be performed prior to installing the support rack-mount brackets.
Position one of the support rack-mount brackets in the rack and adjust it to the depth of the cabinet rack.
Step 2
Repeat this step for the other side. Use the screws to secure the brackets but do not tighten them yet.
OL-17467-02
One AC power connection @110 VAC = No output
Two AC power connection @110 VAC = 2900-W output
One AC power connection @ 220 VAC = 2900-W output
Two AC power connection @ 220 VAC = 6000-W output
lists the items provided in the Cisco MDS 9513 rack-mount kit.
Contents for the Rack-Mount Support Bracket Kit
Part Description
Rack-mount support bracket
Rack-mount support bar
12-24 x 3/4-in. Phillips screws
10-32 x 3/4-in. Phillips screws
"Removing, Installing, and Verifying Supervisor, Switching, and
for instructions specific to the component.
Cisco MDS 9500 Series Hardware Installation Guide
Installing the Chassis in a Cabinet or Rack
2-7