Removing An Ac Power Supply From The Cisco Mds 9509 Director - Cisco AJ732A - MDS 9134 Fabric Switch Installation Manual

Cisco mds 9500 series hardware installation guide (ol-17467-02, october 2008)
Hide thumbs Also See for AJ732A - Cisco MDS 9134 Fabric Switch:
Table of Contents

Advertisement

Removing and Installing a Power Supply or PEM
S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m .
See

Removing an AC Power Supply from the Cisco MDS 9509 Director

The procedure for removing an AC power supply from the Cisco MDS 9509 Director is the same for the
4000-W, 3000-W, and 2500-W power supplies, except the power cable for the 4000-W power supply is
hard wired to the power supply.
Warning
Voltage is present on the backplane when the system is operating. To reduce risk of an electric shock,
keep hands and fingers out of the power supply bays and backplane areas. Statement 166
To remove an AC power supply from the Cisco MDS 9509 Director, follow these steps:
Turn the power switch on the power supply to the off (0) position. Turning the power switch off also
Step 1
unlocks the power supply from the chassis.
Disconnect the power cable from the power source.
Step 2
Loosen the screw on the cable retention device and disconnect the power cable from the power supply
Step 3
being removed.
Note
Loosen the captive screw.
Step 4
Caution
Step 5
Grasp the power supply handle with one hand, and slide the power supply partially out of the chassis.
Place your other hand underneath the power supply, as shown in
completely out of the chassis.
If the power supply bay is to remain empty, install a power supply filler panel over the opening, and
Step 6
tighten the captive screw to 8 in-lb.
Cisco MDS 9500 Series Hardware Installation Guide
2-56
Table 1-2 on page 1-11
for power supply LED details.
The AC power cable for the 4000-W power supply is hardwired and cannot be removed from the
power supply.
Use both hands to install and remove power supplies. Each Cisco MDS 9500 Series AC power
supply weighs between 22 lb (9.9 kg) and 28 lb (12.6 kg).
Chapter 2
Installing the Cisco MDS 9500 Series
Figure
2-30, and slide the power supply
OL-17467-02

Advertisement