The FACP must be programmed for annunciators whenever it is connected to a UDACT because the UDACT
receives the FACP status on the EIA-485 annunciator port. Refer to the table below for typical EIA-485 annunciator
port configurations.
FACP
Size (Points)
Annun. Mode
1 to 64
1 to 64 points
Dual 1 to 64
1 to 64
Dual 1 to 64
1 to 64
Quad 1 to 64
1 to 64
65 to 128
65 to 128 points
Dual 1 to 128
65 to 128
Dual 1 to 128
65 to 128
All S5000
systems with
AIM, 256 points
AIM point
annunciation
All S5000
systems with
AIM, 256 points
AIM point
annunciation
Notes:
1)
UDACT requires software P/N 73624 or higher.
2)
The wiring to Receive Only annunciators will be supervised if the wiring is connected sequentially and a Receive/Transmit device
is the last item connected to both the power and the EIA-485 circuits. The Receive/Transmit device functions as an End-of-Line
Device.
3)
The UDACT's output (TB3-2) must be monitored by the FACP. Comm Fail can be connected to the FACP via the Aux Trouble Input
on the Main Power Supply (P5-1 on MPS-24A or P4-1 on the MPS-24B). See Connections diagrams.
Trouble
Software P/N 73451
Point
and lower
(Yellow LED)
1
System Trouble
2
Signal Silenced
3
Not Used
4
Supervisory
Notification Circuit 1
5
Trouble
Notification Circuit 2
6
Trouble
Municipal Tie
7
Trouble
8
Panel Trouble
AMG
Not Installed
Not Installed
points
Receive/Transmit
points
Address 1 (fixed)
Receive/Transmit
points
Address 1 (fixed)
Not Installed
Not Installed
points
Receive/Transmit
points
Address 1 (fixed)
Not Installed
Receive/Transmit
Address 1 (fixed)
S5000 15583 Rev.
Software P/N 73610 and higher
Without UDACT
System Trouble
(less AC loss)
Signal Silenced
Not Used
Supervisory
Notification Circuit 1
Notification Circuit 1
Trouble
Notification Circuit 2
Notification Circuit 2
Trouble
Municipal Tie
Low Battery/Gnd
Trouble
AC Fail
UDACT (note 1)
Receive/Transmit
Start Monitor Address 1
Stop Monitor Address 1
Receive/Transmit
Start Monitor Address 2
Stop Monitor Address 2
Receive/Transmit
Start Monitor Address 2
Stop Monitor Address 2
Receive/Transmit
Start Monitor Address 2
Stop Monitor Address 2
Receive/Transmit
Start Monitor Address 1
Stop Monitor Address 2
Receive/Transmit
Start Monitor Address 1
Stop Monitor Address 2
Receive/Transmit
Start Monitor Address 3
Stop Monitor Address 4
Receive/Transmit
Start Monitor Address 1
Stop Monitor Address 4
Receive Only
Start Monitor Address 1
Stop Monitor Address 4 (note 3)
6/10/96 P/N 15583:
With UDACT
System Trouble
(less AC loss)
Signal Silenced
Not Used
Supervisory
Trouble
Trouble
Fault
AC Fail
Annunciator (note 2)
Not Installed
One Receive/Transmit Annunciator at Address 1.
Additional annunciators may be employed in the
Receive Only Mode, also at Address 1.
Annunciators, set to address 1 or 2, may be
employed in the Receive Only Mode
Two annunciators must be installed in the
Receive/Transmit Mode. One at address 3 and
one at address 4. Additional annunciators may be
employed in the Receive Only Mode.
Not Installed
A 128 point annunciator, set to address 3 and 4,
must be installed in the Receive/Transmit Mode.
Additional annunciators may be employed in the
Receive Only Mode.
An annunciator must be installed at address 2 in
the Receive/Transmit Mode
Annunciator, set to address 1, 2, 3 and/or 4 may
be employed in the Receive Only Mode
Annunciators, set to address1, 2, 3 and/or 4 may
be employed in the Receive Only Mode
55