Pittway System Sensor SS12ADA Series Installation And Maintenance Instructions Manual

Strobes and horn/strobes for fire protective signaling systems

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SS12/24ADA* Series Strobes and
MASS12/24ADA* Series Horn/Strobes
for Fire Protective Signaling Systems
*ULC models add suffix "A"; strobes and sounder/strobes available in 24VDC,
15cd only
Table 1. SS12/24ADA Series electrical ratings:
Model
Supply
Operating Current from Regulated Supply
Voltage
Range
Average
Peak
Operating
Current
Current
(mA)
20/30V
SS24110ADA
20-30V
210
470/500
SS24110ADAB
SS2475ADA
20-30V
170
385/400
SS2475ADAB
SS2415ADA
20-30V
75
160/180
SS2415ADAB
SS1215ADA
10.5-17V
170
-
SS1215ADAB
SS241575ADA
20-30V
93
210/220
SS241575ADAB
SS121575ADA
10.5-17V
225
--
SS121575ADAB
20-30V
175
360/380
SS2415ADAA
General Description
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, local codes,
and any special requirements of the local fire authority hav-
ing jurisdiction.
The Multi-Alert sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
listed fire alarm control panel. Both are compatible with DC
line supervision. The electronic sounder can be connected
Table 2. Sound Output and Current Ratings for the MA12/24D:
Sound (Hz)
Slow Whoop
800 Continuous
800/1000 Alternating
2400 Interrupted
2400 Continuous
1200 Interrupted
Swept Frequency
Fast Warble
Note 1:
See Figure 2 for tab clip removal & storage.
Note 2:
All models can be powered using full wave rectified unfiltered
supplies.
Under
no
MASS24ADA series devices input voltage exceed 33 VDC or be
less than 16 VDC (16-33Vrms for full-wave rectified, unfiltered
supplies).
Under no circumstances can the MA12/24D input
D900-01-00
Operating Current from Full-Wave Rectified Unfiltered
Peak
Inrush
Average
Peak Current
Current
Current
Operating
(mA)
(mA)
(mA in
Current
20Vrms/
30Vrms
10.5V/17V
access of
(mArms)
Peak)
-
0
245
400/500
-
0
200
320/370
-
0
90
275/290
360/380
0
200
-
--
0
120
275/290
510/560
0
270
--
--
0
200
330/380
Clips on Tabs
Current (ma)
DC Regulated/
( Note 1)
FWR Unfiltered
12V
ABC
21/40 38/56 46/72
BC
15/24 28/45 35/55
AC
17/32 34/46 43/58
AB
19/23 35/56 43/64
C
21/31 38/59 46/73
B
13/19 23/33 27/41
A
17/24 34/47 43/60
NONE
15/27 30/47 38/59
circumstances
can
SS24ADA
Supply
Peak Current
Inrush Current
(mA)
(Amps in excess
10.5Vrms/
of Peak)
17Vrms
-
.080
-
.040
-
.020
330/380
.020
--
1.0
500/530
.020
--
.020
to either 12 or 24 VDC panels. Models SS2415ADA,
SS2475ADA, SS24110ADA, SS241575ADA, and combina-
tion models incorporating these strobes, require 24 volt
panels.
Models
MASS1215ADA , and MASS121575ADA require 12 volt pan-
els. Panels may have full-wave rectified, unfiltered power
supplies. The strobes produce one flash per second (nomi-
nal) with continuous nominal voltage applied.
The MA12/24D is suitable for outdoor applications (-35° to
66° C) when it is used with a WBB Weatherproof Back Box.
The signaling strobe is rated for 0° to 49° C and is NOT
Output (dBA)
(Note 3)
24V
30V
12V
85
87
85
89
85
85
85
85
voltage exceed 33 VDC or be less than 9.6 VDC. Under no cir-
cumstances can a SS12ADA or MASS12ADA series device input
or
voltage exceed 18.7 VDC or be less than 9.6 VDC (9.6 -
18.7Vrms for full-wave rectified, unfiltered supplies).
Note 3:
Measured at 10 feet in an anechoic chamber.
Note 4:
Measured in a UL reverberant room.
1
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTE: Inrush current du-
ration is less than
20
microseconds
(.00002 seconds).
SS1215ADA,
SS121575ADA,
UL (dBA)
Ratings
(Note 4)
24V
12V
24V
92
79
85
93
79
85
92
79
85
90
79
85
94
79
85
91
75
82
92
79
85
92
79
85
I56-650-16

Advertisement

loading
Need help?

Need help?

Do you have a question about the System Sensor SS12ADA Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pittway System Sensor SS12ADA Series

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS SS12/24ADA* Series Strobes and MASS12/24ADA* Series Horn/Strobes A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 for Fire Protective Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 *ULC models add suffix “A”; strobes and sounder/strobes available in 24VDC, 15cd only Table 1.
  • Page 2 suitable for outdoor use. at the device terminal connection in order to main- tain electrical supervision. Strobe and strobe/ The rated light output of the SS2415ADA, SS1215ADA, horn combination are designed for wall mount- SS241575ADA, SS121575ADA, MASS2415ADA, ing ONLY. MASS241575ADA, MASS1215ADA, and MASS121575ADA The sounder is 1-1/4"...
  • Page 3 Figure 1. Vertical and horizontal light distribution: Degrees % of Rating 0˚ 5 - 25 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ Figure 2: Figure 3. Multi-alert sounder: To Next COVER SLOT - VDC TONE SELECTION TABS Device TAB A + VDC TAB B TAB C...
  • Page 4 Figure 8. Strobe surface mount: Figure 9. Sounder/strobe sur face mount: Standard MA-12/24D Backbox Standard Backbox Signal Strobe Signal Strobe 1. Complete field wiring. 1. Complete field wiring. 2. Screw strobe to box with screw A. 2. Screw sounder/strobe to box with screw A. A78-2514-00 A78-2515-00 3.
  • Page 5: Installation And Maintenance Instructions

    INSTALLATION AND MAINTENANCE INSTRUCTIONS SP100ADA Series Dual-transformer Speaker/Strobes for Fire Protective A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Specifications Mechanical Input Terminals: 12 to 18 AWG (3.31 to 0.82 mm Speaker Size:...
  • Page 6 For example, Table 1 shows that to select a 1/4 Watt in- Table 1: put when a 25 volt amplifier is being used, slide the blue 1/2 W 1/4 W 1/8 W lead onto post 3 and slide the yellow lead onto post B. Similarly, to select a 4 Watt input with a 70.7 volt ampli- 25 V fier, slide the blue and yellow leads onto posts 2 and A,...
  • Page 7 NOTE: The light output at 0° viewing angle for Strobe Light Ratings The signaling strobe is rated for 0° to 49° C and is not suit- SP1*241575ADA is 75 cd (See Figure 3). able for outdoor use. R = Red The rated light output of the SP1 2415ADA and W = White...
  • Page 8 WARNING The Limitations of Speaker/Strobes If either of the power option jumper wires is not plugged into one of the Underwriters Laboratories’ standard 1971 and uses an extremely reliable appropriate option positions, the speaker will not sound and there will be xenon flash tube.
  • Page 9 INSTALLATION AND MAINTENANCE INSTRUCTIONS V4R24ADA Series Speaker/Strobes A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 for Fire Protective Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Specifications Speaker Frequency Range: 400 Hz to 4000Hz Supervision: Capacitive input for supervisory DC voltage Mounting: Standard 4"...
  • Page 10 Figure 1. Vertical and horizontal light distribution: Degrees % of Rating 0˚ 5 - 25 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ The light output rating of the Model V4R24110ADA is 110 2. See Figure 2. The speaker is equipped with five posts cd;...
  • Page 11 C. Semiflush Wall Mount Figure 2: (a) System Sensor semiflush mounting plates are shipped with #8 nuts already installed from the 1/4W back. 1/2W (b) Attach the semiflush mounting plate to a standard 4- inch square electrical box using the two 8-32 X 5/8" slotted screws, provided, at diagonally opposite cor- ners, as shown in Figure 4.
  • Page 12 WARNING The Limitations of Speakers and Speaker/Strobes If the power option plug is not plugged into one of the option positions, and must be installed within an area where it can be seen by building oc- the speaker will not sound and there will be no trouble indication at the cupants.
  • Page 13 INSTALLATION AND MAINTENANCE INSTRUCTIONS RK24ADA Series Retrofit Strobes A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 for Fire Protective Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Table 1. RK24ADA Series Electrical Ratings: Model Supply Operating Current from Operating Current from Full-Wave...
  • Page 14 Note : All models can be powered using full wave recti- Mounting Location (per NFPA 72) fied unfiltered supplies. Under no circumstances Sleeping: 110 cd if bottom of appliance is greater than 24" can RK24ADA series devices input voltage exceed below the ceiling, 177 cd if the bottom of the appliance is 33 VDC or be less than 16 VDC (16-33Vrms for full- less than 24"...
  • Page 15 Figure 2. Sounder and strobe operating Figure 3. Sounder and strobe operating in tandem: independently: To Next Caution: Break off P.C.B. Tabs – VDC Non- – VDC To Next Coded STROBE Device + VDC Supply + VDC Device – VDC or EOL Can Be Coded...
  • Page 16 Figure 6. Sounder flush mount (deep box required): Figure 7. Sounder or sounder/strobe semiflush mount with plaster ring: MA 12/24 MA 12/24D BB-D MP-F Plaster Ring Standard MP-SF Backbox A78-1137-22 1. Plaster Ring should be properly mounted to Electrical Box with screws supplied w/box A78-1137-28 2.
  • Page 17 INSTALLATION AND MAINTENANCE INSTRUCTIONS PS12/24ADA Series Strobes with Mini-sounder for Fire Protective A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Table 1. PS12/24ADA Series Electrical Ratings Operating Current from Regulated Supply Operating Current from...
  • Page 18 Greater than 90 dBA measured in anechoic room at 10 feet, Figure 2: 24 volts (see Figure 2 for other voltages); 79 dBA minimum measured in UL reverberant room @ 12V and 82 dBA @ 24V. NOTE: All models can be powered using full wave recti- fied unfiltered supplies.
  • Page 19 Screw types used in Figures 5 – 8 below: A=#6-32x1-1/2" Phillips Oval Head B=#8-32x5/8" Slotted Pan Head C=#6-32x5/8" Slotted Pan Head D=#8 Phillips Oval Head Sheet Metal Figure 5. Sur face mount to single gang box: Figure 6. Semi-flush mount to single gang box: A78-2602-00 A78-2604-00 1) Complete Field Wiring (see Figure 3)
  • Page 21 INSTALLATION AND MAINTENANCE INSTRUCTIONS RP12/24ADA Series Retrofit Strobes for Fire Protective A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Table 1. RP12/24ADA Series electrical ratings: NOTE: In-rush current du- Model Supply Operating Current from Regulated Supply...
  • Page 23 Figure 2. Independent horn/strobe wiring: Figure 3. Combination horn/srtrobe wiring: (-)IN (-)OUT (+)IN (+)OUT – VDC STROBE NON-CODED SUPPLY To Next + VDC To Next Device – VDC Device SOUNDER CAN BE – VDC or EOL CODED + VDC SUPPLY or EOL + VDC From...
  • Page 24: Label Placement

    Inverted Installation 1. Remove strobe unit by inserting a screwdriver behind the 4. Snap strobe unit back into place noting the alignment of locking tabs, and gently pry the tabs inward (see Figure 5). the text on the back of the strobe unit (see Figure 7). 2.
  • Page 25 INSTALLATION AND MAINTENANCE INSTRUCTIONS SS24ADAS Series Strobes and MASS24ADAS Series Synchronized A Division of Pittway Horn/Strobes for Fire Protective 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Signaling Systems Table 1. SS24ADAS Series Electrical Ratings: NOTE: In-rush current du-...
  • Page 26 The sound selected determines the maximum current and All strobes must be mounted so that the top of the lens is sound power output per device. SeeTable 2 for these val- 24 inches (61 cm) below ceilings or as required by the ues.
  • Page 27 Figure 1. Vertical and horizontal light distribution: Percent of Degrees Rating 5 - 25 0˚ 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ NOTE: ALL STROBES THAT ARE TO BE IN SYNC MUST BE ON THE SAME POWER CIRCUIT. Figure 2: Figure 3.
  • Page 28 Figure 9. Strobe surface mount: Figure 10. Sounder/strobe sur face mount: 1. Complete field wiring. 2. Screw strobe to box with screw A. Standard MA-12/24D Backbox 3. Fill remaining holes with Screw B. Standard Signal Strobe Backbox Signal Strobe 1. Complete field wiring. 2.
  • Page 29 INSTALLATION AND MAINTENANCE INSTRUCTIONS SS24ADAS Series Strobes and MAEH24ADAS Series Synchronized A Division of Pittway Electromechanical Horn/Strobes for 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Fire Protective Signaling Systems Table 1. SS24ADAS Series Electrical Ratings: NOTE: In-rush current du-...
  • Page 30 The sound selected determines the maximum current and All strobes must be mounted so that the top of the lens is sound power output per device. SeeTable 2 for these val- 24 inches (61 cm) below ceilings or as required by the ues.
  • Page 31 Figure 1. Vertical and horizontal light distribution: Percent of Degrees Rating 5 - 25 0˚ 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ NOTE: ALL STROBES THAT ARE TO BE IN SYNC MUST BE ON THE SAME POWER CIRCUIT. Figure 2: Figure 3.
  • Page 32 Figure 9. Strobe surface mount: Figure 10. Sounder/strobe sur face mount: 1. Complete field wiring. 2. Screw strobe to box with screw A. Standard MA12/24EH Backbox 3. Fill remaining holes with screw B. Standard Signal Strobe Backbox Signal Strobe 1. Complete field wiring. 2.
  • Page 33 INSTALLATION AND MAINTENANCE INSTRUCTIONS SpectrAlert Horns, Strobes, and Horn/Strobes A Division of Pittway For use with the following models: 3825 Ohio Avenue, St. Charles, Illinois 60174 Horns: 12/24 volt: H12/24*, H12/24W* 1-800-SENSOR2, FAX: 630-377-6495 Strobes: 12 volt: S1215, S121575, S1215W, S121575W...
  • Page 34 Strobe Only: AVERAGE CURRENT (mA) PEAK CURRENT (mA) IN RUSH CURRENT (mA) 12V Models 24V Models 12V Models 24V Models 12V Models 24V Models 10.5V 10.5V 10.5V Candela 133 159 114 157 81 128 79 460 460 450 460 420 480 150 270 150 270 140 250 80 108 92 124 140 190 170 230 220 280 270 370 15/75...
  • Page 35 System Operation: Non-Synchronized Devices Figure 1. Any combination of models powered by a 2-wire Figure 2. Any combination of models powered by a 4-wire circuit: circuit to provide independent horn and strobe operation (Remove factory installed jumpers, see Figure 4): HORN HORN/STROBE STROBE ONLY...
  • Page 36 Screw types used for mounting: Mounting Diagrams: A = #8 x 1-1/4 plastite Strobe or Horn/Strobe with small footprint mounting plate: B = 6-32 x 1-3/8 oval head C = 6-32 x 1-5/16 pan head S-MP 2-INCH BACK BOX D = #6 plastite E = 8-32 x 3/4 flat head Horn surface mount: 4-INCH BACK BOX...