INSTALLATION AND MAINTENANCE INSTRUCTIONS
V4R24ADA Series Speaker/Strobes
for Fire Protective Signaling Systems
Specifications
Speaker
Frequency Range:
Supervision:
Power
Input
Minimum Output (dBA)
Tap
Voltage
(Watts)
(Vrms)
UL
Reverberant
25 or 70.7 1/4
75
25 or 70.7 1/2
78
25 or 70.7
1
81
25 or 70.7
2
84
Strobe
Model
Supply
Operating Current from
Voltage
Range
Average
Operating
Current
V4R24110ADA
20-30V
V4R2475ADA
20-30V
V4R2415ADA
20-30V
V4R241575ADA
20-30V
NOTE: Inrush current duration is less than 20 microseconds (.00002 seconds).
General
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the appliances described in these instructions. It
is recommended that the installer become familiar with
these standards and practices, local codes, and any special
requirements of the authority having jurisdiction.
The speakers can operate at any one of four input power
levels at either of two input voltages. The system voltage
and sound power levels are selected at the time of installa-
tion, but can be changed, if necessary.
D900-02-00
400 Hz to 4000Hz
Capacitive input for supervisory DC voltage
Standard 4" X 4" electrical box
Surface mount directly to box
Semiflush mount, using model MP-SF or MP-SFB
Anechoic
@ 10 ft.
78
81
84
87
Regulated Supply
Peak
Inrush
Current
Current
(mA)
(mA in
20/30V
access
of Peak)
210
470/500
0
170
385/400
0
75
160/180
0
93
210/220
0
firealarmresources.com
Operating Current from Full-Wave
Rectified Unfiltered Supply
Average
Peak
Operating
Current
(Amps in
Current
(mA)
(mArms)
20Vrms/
30Vrms
of Peak)
245
400/500
200
320/370
90
275/290
120
275/290
The speaker is also equipped with a capacitive input to al-
low for DC supervision.
An attached 24 VDC strobe at 110, 75, 15, or 15/75 candela
(cd) is also included with the speaker. Although they are
assembled into a unit, the strobe and speaker are electri-
cally independent and require separate power sources.
Strobes can be powered by means of a full-wave rectified
unfiltered supply.
1
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Inrush
Current
excess
0.08
0.04
0.02
1.0
I56-655-03