Troubleshooting
/i
RUN
ALARM
Probable cause
Not Lit Not lit
Initialization in progress
Flashing Fatal system error during initializa-
tion
Lit
Fatal error during operation
Lit
Not Lit
No error
Lit
One of these MECHATROLINK-II
protocol violations:
Parameter out of range
Communication lost
6.7.4
SmartSlice I/O errors
/i
TS
Color
Probable cause
Not Lit
N/A
No power supply
PROGRAMMING MANUAL
Correction
N/A
Replace the unit
Restart the unit. If the problem
persists, replace the unit.
N/A
Restart the TJ2-MC64
Execute the command
MECHATROLINK(unit,0)
Correction
Refer to section 6.7.1
TS
Color
Probable cause
Flashing
Green Adding SmartSlice I/O Units to
(every
the network
second)
There can be a break in the con-
nection between individual
slices, or one of the SmartSlice
sockets is not connected prop-
erly to its left neighboring con-
nector.
The TS LED on all correctly con-
nected slices are flashing, but
the TS LED on the not correctly
connected units are off.
The last unit is not or not prop-
erly connected. The SmartSlice
communication does not start
up.
The TS LED on all SmartSlice I/
O Units are flashing.
Red
SmartSlice bus communication
error
When the registration table
function is enabled, the actual
configuration does not match
the registered configuration
The total number of I/O points in
the SmartSlice I/O systems is
greater than the maximum
Flashing
Green Restore operation in progress
(every
0.5 sec-
Backup operation in progress
onds)
Correction
Wait until the SmartSlice I/O Units
are added to the network
Check the connection between
slices at the point where the first unit
is located with its TS LED off.
Make sure that all slices are con-
nected correctly to each other.
Check the connection of the last unit
and make sure that it is correctly
connected to the SmartSlice system
Make sure that the base block of the
SmartSlice I/O System is connected
properly
Correct the configuration and turn
the power on again
Correct the unit configuration and
number of I/O points and turn the
power on again
Wait until the restore operation is
complete
Wait until the backup operation is
complete
348