System integration
Designation
Extended Ordercode
ENP_VERSION
Device Type
Simulation Switch Output
(OU1)
Simulation Current Output
(OU2)
Simulation switch output
(OU2)
Device search
Operating Mode (FUNC)
Unit changeover (UNI)
Zero point configuration
(ZRO)
Zero point adoption (GTZ)
Damping (TAU)
Lower Range Value for 4
mA (STL)
Upper Range Value for 20
mA (STU)
Pressure applied for 4mA
(GTL)
Pressure applied for 20mA
(GTU)
Alarm current (FCU)
32
8.2
Reading out and writing device data (ISDU – Indexed
Service Data Unit)
Device data are always exchanged acyclically and at the request of the IO-Link master.
Using the device data, the following parameter values or device statuses can be read out:
8.2.1
Endress+Hauser-specific device data
ISDU
ISDU
Size
(dec)
(hex)
(byte)
259
0x0103
60
257
0x0101
16
256
0x0100
2
85
0x0055
66
0x0042
1
86
0x0056
1
87
0x0057
1
88
0x0058
1
67
0x0043
1
68
0x0044
4
69
0x0045
1
70
0x0046
2
71
0x0047
4
72
0x0048
4
73
0x0049
1
74
0x004A
1
75
0x004B
1
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Data type
Access Default
value
String
r/-
String
r/-
36587
Uinteger16 r/-
0x92FE
r/w
Off
uint
r/w
Off
uint
r/w
Off
uint
r/w
Off
uint
r/w
1
uint
r/w
int
r/w
0
uint
-/w
uint
r/w
20
int
r/w
0
int
r/w
10000
uint
-/w
uint
-/w
uint
r/w
MAX
Value range
Offset /
Gradient
0 ~ off,
1 ~ low,
2 ~ high,
4 ~ 4 mA,
5 ~ 8 mA,
6 ~ 12 mA,
7 ~16 mA,
8 ~ 20 mA,
9 ~ 21.95 mA,
otherwise 3.5 mA
0 ~ off,
1 ~ low,
2 ~ high
0 ~ off
1 ~ on
0 ~ off,
1 ~ I,
2 ~ PNP
0 ~ bar,
1 ~ kPa,
2~ psi,
3~ MPa
in 00.00%, default
0.00%
in 000.0 sec, default
0 / 0.1
2.0 sec
in 00.00%, default
bar: 0 / 0.001
0.00%
kPa: 0 / 0.1
MPa: 0 /
0.0001
psi: 0 / 0.01
in 00.00%, default
bar: 0 / 0.001
100.00%
kPa: 0 / 0.1
MPa: 0 /
0.0001
psi: 0 / 0.01
0 ~ MIN,
1 ~ MAX,
2~ HOLD
Data
storage
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
No
Yes
Endress+Hauser
Need help?
Do you have a question about the IO-Link Ceraphant PTC31B and is the answer not in the manual?