Reading Out And Writing Device Data (Isdu - Indexed Service Data Unit) - Endress+Hauser Liquiphant FTL31 IO-Link Operating Instructions Manual

Point level switch for liquids
Hide thumbs Also See for Liquiphant FTL31 IO-Link:
Table of Contents

Advertisement

System integration
The remaining 14 bits contain the value for the fork frequency [0 to 100 %]. A conversion is
not necessary.
Bit
Process value
15
OU2
14
OU1
0 to 13
Raw value, not coverage [0 to 100]
The fork frequency is provided by the device as int13. The decimal separator must then still be
determined using a gradient.
9.2
Reading out and writing device data (ISDU – Indexed Service
Data Unit)
Device data are always exchanged acyclically and at the request of the IO-Link master. Using
the device data, the following parameter values or device statuses can be read out:
9.2.1
Endress+Hauser-specific device data
Designation
ISDU (dec)
ISDU (hex)
Extended order code
259
0x0103
ENP_VERSION
257
0x0101
Device Type
256
0x0100
Forkfrequency
79
0x004F
Simulation Switch
Output 1 (OU1)
89
0x0059
Simulation Switch
Output 2 (OU2)
68
0x0044
24
Size (byte)
Access Default
Data type
value
60
r/-
String
16
r/-
02.03.00
String
2
r/-
0x92FD
Uinteger16
2
r/-
UInt16
1
r/w
0~off
UInt8
1
r/w
0~off
UInt8
Value range
Offset/
gradient
0 to 1300
0 / 0.02
0 ~ off
0 / 0
1 ~ ou1 = high
2 ~ ou1 = low
0 ~ off
0 / 0
1 ~ ou1 = high
2 ~ ou1 = low
Liquiphant FTL31 IO-Link
Value range
0 = open
1 = closed
0 = open
1 = closed
Integer
Data
Range
storage
limits
No
No
0..2
No
0..2
Endress+Hauser