System Integration; Process Data; Reading Out And Writing Device Data (Isdu - Indexed Service Data Unit) - Endress+Hauser Liquipoint FTW33 Operating Instructions Manual

Conductive and capacitance point level measurement
Table of Contents

Advertisement

Liquipoint FTW33
Designation
ISDU
(dec)
Extended order code
259
ENP_VERSION
257
Device Type
256
1)
ε
- Media
104
r
Get Calibration 1/2
87
1)
[Button]
Simulation Switch Out-
89
put (OU1)
Endress+Hauser
9

System integration

9.1

Process data

The device has two switch outputs. Both outputs are transmitted as process data via IO-
Link.
• In the SIO mode, switch output 1 is switched at pin 4 of the M12 plug. In the IO-Link
communication mode, this pin is reserved exclusively for communication.
• In addition, switch output 2 is always switched at pin 2 of the M12 plug.
• The process data of the point level switch are transmitted cyclically in 16-bit chunks.
Bit
0 (LSB)
Device
Coverage [0 to 100 %], resolution approx. 0.1 %
Bit 14 reflects the status of switch output 1 and bit 15 the status of switch output 2. Here,
the logical state "1" at the specific switch output corresponds to "closed" or 24 V
The remaining 14 bits contain the value for the coverage [0 to 100 %] following
conversion using the factor 0.1.
Bit
Process value
14
OU1
15
OU2
0 to 13
Coverage [0 to 100 %]
In addition, the coverage value can be read via ISDU (hex) 0x0028 – acyclic service.
9.2
Reading out and writing device data (ISDU – Indexed
Service Data Unit)
Device data are always exchanged acyclically and at the request of the IO-Link master.
Using the device data, the following parameter values or device statuses can be read out:
9.2.1
Endress+Hauser-specific device data
ISDU
Size
Data
(hex)
(byte)
type
0x0103
60
String
0x0101
16
String
0x0100
2
Uin-
teger16
0x0068
2
Uint16
0x0057
1
UInte-
gerT
0x0059
1
UInt8
1
...
12
Access Default
Value range
value
r/-
r/-
r/-
0x91FC
r/w
13
-/w
1 ~ Get Cali-
bration
r/w
Off
0 ~ Off
1 ~ ou1 =
high
2 ~ ou2 = low
System integration
13 (MSB)
14
OU1
DC
Value range
0 = open
1 = closed
0 = open
1 = closed
Integer
Offset/Gradi-
Data
Range limits
ent
stor-
age
0/0.01
Yes
1.9 to 85
No
0/1
No
0 to 2
15
OU2
.
21