Installation Instructions - Endress+Hauser Ceraphant T PTC31 Operating Instructions Manual

Pressure switch
Hide thumbs Also See for Ceraphant T PTC31:
Table of Contents

Advertisement

Ceraphant T PTC31, PTP31, PTP35
3.4

Installation instructions

For typical possibilities for installing the Ceraphant T - see the diagram below:
• Pressure measurement in gases (left)
Mount Ceraphant T with shut-off assembly above the sampling nozzle so that any condensate
can drain off into the process.
• Pressure measurement in steam (centre)
Mount Ceraphant T with U-pipe below the sampling nozzle. Fill the U-pipe with fill fluid
before commissioning.
• Pressure measurement in liquids (right)
Mount Ceraphant T below or at the same level as the sampling nozzle.
Fig. 3: Possibilities for installing to measure pressure in gases, steam and liquids.
➀ Ceraphant T
➁ Shut-off assembly
➂ U-pipe
Mounting instructions:
• Do not mount the device in the product flow or at a point where it could be affected by
pressure pulses
• Calibration and functional testing are easier if the device is mounted downstream of a shut-off
assembly
• The orientation of the Ceraphant T can result in zero point shift, i.e. in an unpressurised state,
the measured value does not display zero. This zero point shift can be corrected - see
"Operation" section
• The on-site display can be rotated electronically 180° - see "Operation" section
• The housing can be rotated up to 310°
• Process connection G ½A, flush mounted, max. torque 40 Nm (with PTP31)
Endress+Hauser
P01-PTx3xxxx-11-xx-xx-xx-001
Installation
7