Installation
Installation conditions
!
26
3.2

Installation instructions

Liquicap M FTI51 (rod probe) can be installed from above, from below and from the side.
Liquicap M FTI52 (rope probe) can be installed vertically from above.
Note!
• The probe may not come into contact with the container wall! Do not install probes in the area
of the filling curtain!
• When using in agitating tanks, make sure you install at a safe distance from the agitator.
• If there are strong lateral loads, use rod probes with ground tube.
For electrically conductive tanks e.g. steel tanks
MAX
MAX
MIN
MIN
For nonconductive tanks e.g. plastic tanks
MAX
MAX
Probes with ground tube and grounding
Liquicap M FTI51, FTI52
MAX
MAX
MIN
MIN
MAX
MAX
MIN
MIN
L00-FTI5xxxx-11-06-xx-xx-001
L00-FTI5xxxx-11-06-xx-xx-002