Liquiphant FTL51B
Endress+Hauser
13.1.4
M12 connecting cable
A
1
2
3
A
DC-PNP
B
NAMUR and DC-PNP
Order number:
Function:
• Green light (3) is lit:
Liquiphant is connected to the power supply and is ready for operation.
• Yellow light (1) is lit:
MAX mode of operation (overfill prevention): sensor is not immersed in liquid.
MIN mode of operation (dry running protection): sensor is not immersed in liquid.
• Yellow light (2) is lit:
MAX mode of operation (overfill prevention): sensor is immersed in liquid.
MIN mode of operation (dry running protection): sensor is immersed in liquid.
• Green light (3) is lit, the two yellow lights (1+2) are not lit:
Liquiphant has detected an error.
13.1.5
Bluetooth module
Including battery for NAMUR electronics version
13.1.6
LED module
In preparation.
13.2
Sliding sleeves for unpressurized operation
Switch point, infinitely adjustable.
41
G 1 A
(1 NPT)
1
p
= 0 bar (0 psi)
e
M6 (3x)
G 1½ A
(1½ NPT)
Accessories
B
55
M6 (3x)
A0038278
1
A0037666
51