7.4 Cooling Water Flow Rate

* Operating pressure range for optional cooling systems: 29-116 psig (2-8 bar)

Table 13 Water Flow Rates Required For Optional Cooling Systems

WATER COOLING
MODEL
90 W
110 W
132 W
160 W
185 W
200 W
250 W
315 W
HYBRID COOLING
MODEL
90 HC
110 HC
132 HC
160 HC
185 HC
200 HC
250 HC
315 HC
All publication rights of this instruction manual belong to HERTZ KOMPRESSOREN. The manual cannot be reproduced, changed or distributed wholly or partially in any way.
HERTZ KOMPRESSOREN has the legal rights of this user manual and all instructions or parts. Any sampling, sharing or copying are prohibited.
FLOW RATE (gal/min)
ΔT 18 °F
34.55
42.16
50.56
61.34
70.37
76.56
95.73
120.62
FLOW RATE (gal/min)
ΔT 45 °F
ΔT 54 °F
13.79
11.57
16.96
14.11
20.29
16.96
24.57
20.45
28.21
23.46
30.75
25.68
38.52
32.02
48.50
40.42
ΔT 27 °F
22.98
28.05
33.76
40.89
47.07
51.20
63.88
80.52
ΔT 72 °F
ΔT 90 °F
8.56
6.82
10.62
8.40
12.68
10.14
15.37
12.20
17.59
14.11
19.18
15.37
23.93
19.18
30.27
24.09