5 Logging
5-2

K6PM Logging

The Logging Screen for K6PM is described below.
K6PM Logging Screen
Area
A
Logging Interval
B
Logging Target Data
Icon
50
A
Item
1 minute, 10 minutes, 30 minutes, 1 hour, or 6 hours
Displays sensors with completed basic settings.
The following items can be selected for segments (00-15) and sensors
(1-31).
Sensors: internal temperature value, internal maximum temperature value,
Segments: current temperature value, maximum temperature value, pre-
dicted arrival temperature value
Refer to the K6PM-TH User's Manual (N231) for details on the status.
Critical
This is displayed when the comprehensive temperature alarm (threshold 2 exceeded) is 1 (ON)
in the latest log data
(Flashing: predicted arrival temperature exceeded)
Warning
This is displayed when the comprehensive temperature alarm (threshold 1 exceeded) is 1 (ON)
in the latest log data
(Flashing: predicted arrival temperature exceeded)
Communications Error
This is displayed in the following cases:
• When the logging time times out
• When an error response is received
B
Description
Description