4 Alarm Settings
3
Set the thresholds
You can use the Automatic threshold calculation
function.
How to use Automatic threshold calculation
(1) After resetting the maximum temperature, con-
duct monitoring for several days. Measuring
other objects (such as human bodies) than the
intended target or misalignment of the monitor-
ing position may affect the automatic threshold
calculation.
(2) For the max. ambient temperature, enter the
temperature corresponding to the max. ambient
temperature in the control panel, considering
seasonal temperature variations.
(3) Click the Calculation Button.
4
The Button is enabled for clicking when the reading or writing is successfully completed or when
the settings for the screen are completed.
For details on setting parameters, hover your mouse over the "i" mark on the screen to display
hints and instructions. Set the parameters according to those instructions.
Icon
44
Threshold 1 exceeded
This is a warning level notification. When setting with Automatic threshold calculation, the
minimum temperature that recommends immediate maintenance is automatically set.
Threshold 2 exceeded
This is a critical level notification. When setting with Automatic threshold calculation, the
minimum temperature that recommends immediate maintenance is automatically set.
Connection status
Disconnection status
Temperature measurement range exceeded
Measurement temperature: 200.0°C min.
Sensor internal temperature: 80°C min.
The detection of the K6PM-TH sensor
If the angle deviates by more than 5 degrees and this continues for more than 3 seconds.
Threshold settings for each segment of K6PM
Description
Condition Monitoring Configuration Tool Usage Guide (N240)

Advertisement