15.2.5.3 Set Minimum/Maximum speeds
Min/Max Speed parameters are used to set Min/Max speed from PROFIBUS interface:
Values must only be used if matching bit in Control Word is enabled and not zero.
Values are 16 bit unsigned in deci RPM (1/10th of pumphead RPM).
If pump is required to operate at lower speed than user defined minimum
speed parameter data, (bytes 3, 4) pump will operate at defined minimum
speed.
If maximum speed configured in user parameter data, pump is limited to
this maximum speed even when master requests a higher rpm.
15.2.5.4 Fail safe
The fail-safe user parameter is used to set the correct course of action to take in the event of a
PROFIBUS communications failure. The fail-safe byte is configured as shown in the following
1
table
.
1
NOTE
If no bits set or invalid pattern is set, default fail safe behaviour stops pump
Hex
0x00
0x01
0x02
15.2.5.5 Fail safe speed
Fail-safe speed parameter used to set speed at which pump should be driven if a PROFIBUS
communications error occurs and fail- safe user parameter is set to 0x02.
Description
No fail safe action
Continue running using the last speed set point
Continue running using the fail-safe speed