Replace A Failed Drive (Hdd) - HPE Nimble Storage HF Series Hardware Manual

Table of Contents

Advertisement

4. Insert the replacement drive into the drive carrier.
5. Close the sled handle.
Push the handle until it fully engages with the release tab.
6. After no more than two minutes, make sure that the drive (B or A) is green.
If the LED does not light, remove and reinsert the drive. If unsuccessful, contact HPE Support.
7. Replace the bezel.
Hold the bezel in place and then firmly press the bezel until you feel the keepers lock.
8. Return the failed drive as directed on the RMA work order.

Replace a Failed Drive (HDD)

Use this procedure to replace HDDs in your HPE storage array or expansion shelf.
Before you begin
Time required:
Parts required:
Tools required:
Information required:
Support contact:
HPE recommends using the Maintenance Window functionality within the HPE InfoSight portal to inform HPE Support of
upcoming maintenance windows.
Refer to https://infosight.hpe.com/dashboards/nimble/wellness/maintenance-windows for more information.
You can disable automated support case generation during planned maintenance from the Manage Maintenance Windows
page. After a maintenance window is set, no further communication with HPE Support is required.
Note:
Before you attempt to replace the drive:
5 to 10 minutes
Replacement drive ordered from HPE
ESD (electrostatic discharge) strap or appropriate grounding device
RMA (Return Materials Authorization) work order
Case number
Array name or serial number
The array serial number can be found on the back of Controller A.
See Support.
Documentation Feedback: doc-feedback-hpe-storage@hpe.com
Maintenance Procedures 76