3.43 Four Way Valve Abnormality (Not Switching)
Applicable
All outdoor unit models
Models
EA
Error Code
Sub code: 14-21
Method of Error
Detect the non-switching of the four way valve according to temperature and pressure.
Detection
Error Decision
When the evaporator is in a condenser-like refrigerant state
Conditions
When the condenser is in an evaporator-like refrigerant state.
Supposed
Defective high pressure sensor
Causes
Defective low pressure sensor
Defective outdoor air thermistor
Defective heat exchanger gas pipe thermistor
Defective heat exchanger liquid pipe thermistor
Defective suction pipe thermistor
Defective compressor suction thermistor
Defective indoor unit thermistor
Defective coil or harness of four way valve
Defective four way valve
Part 6 Service Diagnosis
Troubleshooting by Error Code