Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, press INSPECTION/TEST button for 4 seconds or more to enter field
2. Set mode No. 00 with MODE button.
3. Set the group No. for each group with UP button or DOWN button.
4. Enter the selected group numbers by pressing RESERVE button.
135
Group Address
• Assign the group address and unit number for centralized control.
• The group and unit address can only be set when a centralized controller is connected.
This menu is only visible when a centralized controller is connected.
• The group and unit address can be "set" and "released".
NOTICE
Don't forget to release the group address before disconnecting the centralized controller because the
menu will not be accessible afterwards.
setting mode.