Daikin VRV EMERION REYQ-AATJA Service Manual page 54

Table of Contents

Advertisement

Specifications
Model name (Combination unit)
Model name (Independent unit)
Power supply
1 Cooling
Nominal
capacity
Rated
2 Heating
Nominal
capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Compressor Type
Volume
Number of
revolutions
Motor output
Starting method
Fan
Type
Motor output ×
Number of units
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Suction gas pipe
High/Low pressure
gas pipe
Weight
Sound pressure level
(Reference data)
Sound power level
(Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Standard accessories
Drawing No.
Notes:
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Rated capacity is certified under AHRI standard 1230.
1.
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Rated capacity is certified under AHRI standard 1230.
2.
47
REYQ456AAYDA
REYQ216AAYDA
REYQ240AAYDA
3 phase, 460 V, 60 Hz
456,000 (134)
Btu/h
(kW)
434,000 (127)
513,000 (150)
Btu/h
(kW)
414,000 (121)
Ivory white (5Y7.5/1)
65-3/8 × 68-7/8 × 30-1/8 + 65-3/8 × 68-7/8 × 30-1/8
in. (mm)
(1,660 × 1,750 × 765 + 1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
m³/h
(17.5 + 17.5) + (20 + 20)
r/min
(5,154 + 5,154) + (5,886 + 5,886)
kW
(5.37 + 5.37) + (6.13 + 6.13)
Propeller fan
kW
0.95 × 2 + 0.95 × 2
cfm
14,505 (410.8) + 14,505 (410.8)
(m³/min)
in. (mm)
 3/4 (19.1) C1220T (brazing connection)
in. (mm)
 1-5/8 (41.3) C1220T (brazing connection)
in. (mm)
 1-3/8 (34.9) C1220T (brazing connection)
lbs (kg)
972 (441) + 972 (441)
dB(A)
dB
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
%
lbs (kg)
25.8 (11.7) + 25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
Soft start
Direct drive
72
95
Deicer
1-100
R-410A
4D134613A
SiUS372201EB
REYQ480AAYDA
REYQ240AAYDA
REYQ240AAYDA
3 phase, 460 V, 60 Hz
480,000 (141)
456,000 (134)
540,000 (158)
424,000 (124)
Ivory white (5Y7.5/1)
65-3/8 × 68-7/8 × 30-1/8 + 65-3/8 × 68-7/8 × 30-1/8
(1,660 × 1,750 × 765 + 1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
(20.4 + 20.4) + (20.4 + 20.4)
(6,018 + 6,018) + (6,018 + 6,018)
(6.27 + 6.27) + (6.27 + 6.27)
Soft start
Propeller fan
0.95 × 2 + 0.95 × 2
14,505 (410.8) + 14,505 (410.8)
Direct drive
 3/4 (19.1) C1220T (brazing connection)
 1-5/8 (41.3) C1220T (brazing connection)
 1-3/8 (34.9) C1220T (brazing connection)
972 (441) + 972 (441)
73
95
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
Deicer
1-100
R-410A
25.8 (11.7) + 25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
4D134614A