Daikin VRV EMERION REYQ-AATJA Service Manual page 317

Table of Contents

Advertisement

SiUS372201EB
Seven-segment display
16I-##
_ _ 1
6 0 9
- # #
16J-##
_ _ 1
6 1 0
- # #
16L-##
_ _ 1
6 1 2
- # #
16M-##
_ _ 1
6 1 3
- # #
16N-##
_ _ 1
6 1 4
- # #
16O-##
_ _ 1
6 1 5
- # #
16P-##
_ _ 1
6 1 6
- # #
16Q-##
_ _ 1
6 1 7
- # #
16S-##
_ _ 1
6 1 9
- # #
16U-##
_ _ 1
6 2 1
- # #
16V-##
_ _ 1
6 2 2
- # #
16W-##
_ _ 1
6 2 3
- # #
20A-##
_ _ 2
0 0 1
- # #
30A-##
_ _ 3
0 0 1
# # #
31A-##
_ _ 3
1 0 1
# # #
31B-##
_ _ 3
1 0 2
# # #
31C-##
_ _ 3
1 0 3
# # #
43A-##
_ _ 4
3 0 1
- 0 0
43B-##
_ _ 4
3 0 2
- 0 0
43C-##
_ _ 4
3 0 3
- 0 0
43D-##
_ _ 4
3 0 4
- 0 0
47A-##
_ _ 4
7 0 1
- 0 0
 Depending on operating condition, partial refrigerant shortage may be detected even though
correct refrigerant amount is in the system. Please refer to Refrigerant Shortage Check on page
457 for the analysis.
Part 6 Service Diagnosis
Description
Heat exchanger liquid pipe thermistor
1 failure prediction (Tf1)
Heat exchanger liquid pipe thermistor
2 failure prediction (Tf2)
Compressor suction thermistor failure
prediction (Ts)
Accumulator inlet thermistor failure
prediction (TsA)
Receiver gas purge thermistor failure
prediction (Tgi)
Liquid pipe thermistor failure
prediction (TL)
Heat exchanger gas pipe thermistor 1
failure prediction (Tg1)
Heat exchanger gas pipe thermistor 2
failure prediction (Tg2)
Subcooling injection thermistor failure
prediction (Tm)
Electrical box air outlet thermistor
failure prediction (Tjeva)
High pressure sensor failure
prediction (HP)
Low pressure sensor failure
prediction (LP)
Heat exchanger freeze up prediction
Indoor unit electronic expansion valve
leak (evaporator) prediction
_ _ #
Indoor unit thermistor failure
_ _ #
prediction (Th1)
Indoor unit thermistor failure
_ _ #
prediction (Th2)
Indoor unit thermistor failure
_ _ #
prediction (Th3)
Refrigerant shortage and refrigerant
leakage prediction (detected during
non-operation)
Refrigerant shortage and refrigerant
leakage prediction (detected during
cooling operation)
Refrigerant shortage and refrigerant
leakage prediction (detected during
cooling and heating simultaneous
operation)
Refrigerant shortage and refrigerant
leakage prediction (detecting during
heating operation)
Outdoor-indoor communication failure
prediction
Possible cause
■ Tf1 sensor failure
Refer to J8 troubleshooting.
■ Tf2 sensor failure
Refer to J8 troubleshooting.
■ Ts sensor failure
Refer to J5 troubleshooting.
■ TsA sensor failure
Refer to J5 troubleshooting.
■ Tgi sensor failure
Refer to J9 troubleshooting.
■ TL sensor failure
Refer to J7 troubleshooting.
■ Tg1 sensor failure
Refer to J6 troubleshooting.
■ Tg2 sensor failure
Refer to J6 troubleshooting.
■ Tm sensor failure
Refer to J7 troubleshooting.
■ Tjeva sensor failure
Refer to J9 troubleshooting.
■ HP sensor failure
Refer to JA troubleshooting.
■ LP sensor failure
Refer to JC troubleshooting.
■ Tb sensor failure
Melt frost on the outdoor heat exchanger.
■ Freeze
■ Tb sensor failure
Th1: Refer to C9 troubleshooting.
■ Indoor leakage
Th2: Refer to C4 troubleshooting.
Th3: Refer to C5 troubleshooting.
LP: Refer to JC troubleshooting.
If the above error is not seen, the corresponding
indoor electronic expansion valve and expansion
valve coil can be considered.
■ Th1 sensor failure
Th1: Refer to C9 troubleshooting.
Th2: Refer to C4 troubleshooting.
■ Th2 sensor failure
■ Th3 sensor failure
Th3: Refer to C5 troubleshooting.
Th1: Refer to C9 troubleshooting.
■ Th1 sensor failure
■ Th2 sensor failure
Th2: Refer to C4 troubleshooting.
■ Th3 sensor failure
Th3: Refer to C5 troubleshooting.
■ Th1 sensor failure
Th1: Refer to C9 troubleshooting.
■ Th2 sensor failure
Th2: Refer to C4 troubleshooting.
■ Th3 sensor failure
Th3: Refer to C5 troubleshooting.
■ HP sensor failure
HP: Refer to JA troubleshooting.
■ Refrigerant leak or shortage
If the above error is not seen, refrigerant shortage
or leakage from the system can be considered. ()
■ Refrigerant leak or shortage
Check for refrigerant leakage.
Check for refrigerant shortage. ()
■ Refrigerant leak or shortage
Check for refrigerant leakage.
Check for refrigerant shortage. ()
■ Refrigerant leak or shortage
Check for refrigerant leakage.
Check for refrigerant shortage. ()
■ Outdoor unit control PCB
failure
■ Indoor PCB failure
■ Outdoor-indoor
communication line failure
Troubleshooting by Error Code
Tech tips
310