Daikin VRV EMERION REYQ-AATJA Service Manual page 270

Table of Contents

Advertisement

Field Setting from Outdoor Unit
[2-49]:
[2-51]:
[2-60]:
[2-62]:
Adjust cooling and heating system operation to achieve stable capacity.
Note(s)
This setting may result in a longer reaction time to large load variations.
[2-64]:
[2-71]:
263
Height difference setting
Default value: 0.
In case the outdoor unit is installed in the highest position (indoor units are installed
on a lower position than outdoor units) and the height difference between the lowest
indoor unit and the outdoor unit exceeds 50 m (164 ft), the setting [2-49] has to be
changed to 1.
Master/Sub setting Multi
When 2 modules are installed as a multi-outdoor (by common refrigerant piping and
wiring by terminals Q1Q2) configuration is automatically detected. In certain cases, the
sequence of the Sub unit need to be set manually (in case of AIRNET monitoring).
Default value: 0. Automatic detection.
Field setting: ensure that the modules in a multi are set different status. Even some
modules in a multi are set manually to same status, U7 error will appear.
 1: forced Master (F1F2/Ind terminals should be connected to indoor units).
 2: forced Sub (only Q1Q2 terminals should be wired to Master module).
Gas furnace setting
Default value: 0.
When a gas furnace is connected, the setting [2-60] has to be changed to 1.
Cooling and heating capacity learning control
Default value: 0.
Value
[2-62]
0 (default)
1
2
3
Eco mode invalid setting
Used to make setting of Eco mode invalid. When this configuration is set, it is not
possible to turn Eco mode ON/OFF using external control adaptor or other setting.
Default value: 0.
Value
[2-64]
0 (default)
Activated both cooling and heating
1
2
3
Branch selector switching time
Default value: 0.
Used for changing branch selector switching time.
All piping length between branch selector unit and indoor units should be less than
9.7 m (32 ft).
Description
OFF
Cooling adjustment
Heating adjustment
Cooling and heating adjustment
Eco mode control setting
Activated heating only
Activated cooling only
Deactivated
SiUS372201EB
Part 5 Field Settings and Test Operation