Daikin VRV EMERION REYQ-AATJA Service Manual page 324

Table of Contents

Advertisement

Troubleshooting by Error Code
Note(s)
FXFQ-AA
FXZQ-TA
FXZQ-TB
FXUQ-PA
FXSQ-TA
FXSQ-TB
FXMQ-PB
FXMQ-TB
FXMQ-TA
317
A
The drain
pump works when the
power supply is reset for the
indoor unit.
NO
The
voltage of
drain pump
terminals ( 2) is in
accordance to the criteria
( 3) (within 5 minutes of
resetting the power
supply).
YES
1: Float switch (S1L) /
Model
short circuit connector
X15A
FXFQ-T
X15A
X15A
X15A
FXUQ-P
X15A
X15A
FXEQ-P
X15A
FXDQ-M
X8A
X15A
X15A
X15A
X15A
X15A
YES
NO
2: Drain pump (M1P)
connector
X25A
X10A
X102A
X25A
X25A
X25A
X25A
X25A
X25A
X25A
X25A
X25A
X25A
SiUS372201EB
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit control
PCB (A1P).
Replace the drain pump (M1P)
or check for dirt, etc.
3: Drain pump (M1P)
voltage
13 VDC
13 VDC
13 VDC
13 VDC
13 VDC
13 VDC
13 VDC
220-240 VAC
13 VDC
13 VDC
220-240 VAC
13 VDC
13 VDC
Part 6 Service Diagnosis
Note
Option

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion reyq-aatjbVrv emerion reyq-aaydaVrv emerion reyq-aaydbVrv emerion reyq72aatjaVrv emerion reyq72aaydbVrv emerion reyq72aatjb ... Show all

Table of Contents