Troubleshooting by Error Code
3.19 Self-Cleaning Decoration Panel Abnormality
Applicable
FXFQ-AA (when self-cleaning decoration panel BYCQ54EEGFU is installed)
Models
FXFQ-T (when self-cleaning decoration panel BYCQ125BGW1 is installed)
AH
Error Code
Method of Error
Error is detected by abnormal signal from the self-cleaning decoration panel.
Detection
Error Decision
Any of the following conditions is met while the unit is in operation.
Conditions
There is a transmission error between self-cleaning decoration panel and indoor unit.
Dust detection sensor (light receiving side) is short-circuited.
The total of fan operation time exceeds a specified value after dust collection sign display.
Limit switch does not detect when air filter rotates or air filter does not rotate.
Limit switch does not detect when damper opens (or closes) or damper does not work.
Filter auto clean operation does not complete even after a specified time has elapsed.
Filter auto clean operation does not start even after a specified time has elapsed.
Supposed
Transmission error (between self-cleaning decoration panel and indoor unit)
Causes
Dust detection sensor error
Dust collection sign
Air filter rotation error
Damper rotation error
Filter auto clean operation error
Filter auto clean operation start disabled error
337
SiUS372201EB
Part 6 Service Diagnosis