Discharge Pipe Temperature Abnormality - Daikin VRV EMERION REYQ-AATJA Service Manual

Table of Contents

Advertisement

Troubleshooting by Error Code

3.45 Discharge Pipe Temperature Abnormality

Applicable
All outdoor unit models
Models
F3
Error Code
Method of Error
Detect according to temperature detected with the discharge pipe or compressor body thermistor.
Detection
Error Decision
 When discharge pipe temperature becomes abnormally high (i.e., 135°C (275°F) or more)
Conditions
 When discharge pipe temperature sharply rises (remains at 120°C (248°F) or more for a period
 When compressor surface temperature becomes abnormally high (i.e., 120°C (248°F) or more)
 When compressor surface temperature sharply rises (remains at 115°C (239°F) or more for a
Supposed
 Abnormal discharge pipe temperature
Causes
 Defective discharge pipe thermistor
 Abnormal compressor surface temperature
 Defective compressor body thermistor
 Defective outdoor unit main PCB
383
of consecutive 10 minutes)
period of consecutive 10 minutes)
SiUS372201EB
Part 6 Service Diagnosis