Daikin VRV EMERION REYQ-AATJA Service Manual page 44

Table of Contents

Advertisement

Specifications
Model name (Combination unit)
Model name (Independent unit)
Power supply
1 Cooling
Nominal
capacity
Rated
2 Heating
Nominal
capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Compressor Type
Volume
Number of
revolutions
Motor output
Starting method
Fan
Type
Motor output ×
Number of units
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Suction gas pipe
High/Low pressure
gas pipe
Weight
Sound pressure level
(Reference data)
Sound power level
(Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Standard accessories
Drawing No.
Notes:
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Rated capacity is certified under AHRI standard 1230.
1.
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Rated capacity is certified under AHRI standard 1230.
2.
37
REYQ408AATJB
REYQ192AATJB
REYQ216AATJB
3 phase, 208/230 V, 60 Hz
406,000 (119)
Btu/h
(kW)
388,000 (114)
459,000 (135)
Btu/h
(kW)
388,000 (114)
Ivory white (5Y7.5/1)
65-3/8 × 68-7/8 × 30-1/8 + 65-3/8 × 68-7/8 × 30-1/8
in. (mm)
(1,660 × 1,750 × 765 + 1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
m³/h
(16.3 + 16.3) + (18.5 + 18.5)
r/min
(4,818 + 4,818) + (5,442 + 5,442)
kW
(5.02 + 5.02) + (5.67 + 5.67)
Propeller fan
kW
0.95 × 2 + 0.95 × 2
cfm
13,650 (386.5) + 14,505 (410.8)
(m³/min)
in. (mm)
 3/4 (19.1) C1220T (brazing connection)
in. (mm)
 1-5/8 (41.3) C1220T (brazing connection)
in. (mm)
 1-3/8 (34.9) C1220T (brazing connection)
lbs (kg)
957 (434) + 957 (434)
dB(A)
dB
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
%
lbs (kg)
25.8 (11.7) + 25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
Soft start
Direct drive
71
93
Deicer
1-100
R-410A
4D148472
SiUS372201EB
REYQ432AATJB
REYQ216AATJB
REYQ216AATJB
3 phase, 208/230 V, 60 Hz
430,000 (126)
410,000 (120)
486,000 (142)
404,000 (118)
Ivory white (5Y7.5/1)
65-3/8 × 68-7/8 × 30-1/8 + 65-3/8 × 68-7/8 × 30-1/8
(1,660 × 1,750 × 765 + 1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
(17.7 + 17.7) + (17.7 + 17.7)
(5,232 + 5,232) + (5,232 + 5,232)
(5.45 + 5.45) + (5.45 + 5.45)
Soft start
Propeller fan
0.95 × 2 + 0.95 × 2
14,505 (410.8) + 14,505 (410.8)
Direct drive
 3/4 (19.1) C1220T (brazing connection)
 1-5/8 (41.3) C1220T (brazing connection)
 1-3/8 (34.9) C1220T (brazing connection)
957 (434) + 957 (434)
72
95
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
Deicer
1-100
R-410A
25.8 (11.7) + 25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
4D148472
Part 1 General Information

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion reyq-aatjbVrv emerion reyq-aaydaVrv emerion reyq-aaydbVrv emerion reyq72aatjaVrv emerion reyq72aaydbVrv emerion reyq72aatjb ... Show all

Table of Contents